172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
191
In the event hold state, no event output is turned on even after the Event timer
preset time has elapsed.
The Event timer is reset for the following reasons when:
Power failure occurs while the Event timer is being activated
Control is changed to STOP (control stop) from RUN (control start) while the
Event timer is being activated
Event state is cancelled while the event timer is activated
Parameter setting
Event 1 timer [Engineering Mode: Function block No. 41 (
Fn41
)]
Parameter symbol
Data range
Factory set value
EV T 1
0.0 to 600.0 seconds
0.0
Event 2 timer [Engineering Mode: Function block No. 42 (
Fn42
)]
Parameter symbol
Data range
Factory set value
EV T 2
0.0 to 600.0 seconds
0.0
Event 3 timer [Engineering Mode: Function block No. 43 (
Fn43
)]
Parameter symbol
Data range
Factory set value
EV T 3
0.0 to 600.0 seconds
0.0
Event 4 timer [Engineering Mode: Function block No. 44 (
Fn44
)]
Parameter symbol
Data range
Factory set value
EV T 4
0.0 to 600.0 seconds
0.0
7.1.6 Changing event output assignment
Event output assignment can be changed through OUT1 to 3 function selection, DO1
to 4 function selection, OUT1 to 3 logic calculation selection, and DO1 to 4 logic
calculation selection.
Refer to 6.1 Changing Output Assignment [Control Output, Retransmission
Output, Logic Calculation (Event) Output, Instrument Status Output] for Event
output assignment.
7.1.7 Changing the event set value
The Event set value can be set in Parameter group No. 40 in the Parameter setting
mode. Since the Set value for Event 1 to 4 are included in the Memory area, up to 16
data can be stored per parameter.
Refer to the the SC-F71 Quick Start Guide (172-65706M) or Instruction Manual
[Hardware] (172-65709M) for how to set Event set values.
Refer to10.3 Storing the control related set values (Memory Area function) for
Memory area transfer.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...