172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
242
To display “Input 1_Corrective action repeat”, choose “3 to 7 (Pressure control
operation [MC-
(V)COS(R)])” in Function block No.51: Input 1_Control action
(Engineering mode).
Input 1_ Corrective actions for ramp control [Engineering Mode: Function
block No. 53 (
Fn53
)]
Parameter symbol
Data range
Factory set value
1. Pc 3
0: Yes
1: No
0
Do not change the factory set value.
TLV engineers may change the value to adjust the controllability after
checking the users’ applications and conditions. Unnecessary changes to
values may affect controllability. Please contact TLV for details.
To display “Input 1_Corrective actions for ramp control”, choose “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.51: Input
1_Control action (Engineering mode).
Input 1_ Lower range of corrective action amount [Engineering Mode:
Function block No. 53 (
Fn53
)]
Parameter symbol
Data range
Factory set value
1. oL b
0.0 to 105.0%
20.0
Do not change the factory set value.
TLV engineers may change the value to adjust the controllability after
checking the users’ applications and conditions. Unnecessary changes to
values may affect controllability. Please contact TLV for details.
To display “Input 1_Lower range of corrective action amount”, choose “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.51: Input
1_Control action (Engineering mode).
Input 1_ Upper range of corrective action amount [Engineering Mode:
Function block No. 53 (
Fn53
)]
Parameter symbol
Data range
Factory set value
1. oH b
0.0 to 105.0%
20.0
Do not change the factory set value.
TLV engineers may change the value to adjust the controllability after
checking the users’ applications and conditions. Unnecessary changes to
values may affect controllability. Please contact TLV for details.
To display “Input 1_Upper range of corrective action amount”, choose “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.51: Input
1_Control action (Engineering mode).
Input 1_Dead zone [Parameter Setting Mode: Parameter group No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1.M Cd b
0 to
10% of input_1 span
[Position of decimal point depends of Input 1_Valve coefficient
F]
See Table 8-3
NOTE
NOTE
NOTE
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...