172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
278
When “Switching by level” is set to “Selection of PV select trigger”, the
parameter becomes display only.
PV select transfer level [Setup Setting Mode: Setting group No. 58 (
Sn58
)]
Parameter symbol
Data range
Factory set value
2 P V.L V
Input 1_Input range low to Input 1_Input range high
[Varies with the setting of the Decimal point position.]
Input 1_Input range high
To display “PV select transfer level”, choose “Control with PV select” in Function
block No. 58: Select function for Input 2 (Engineering mode).
PV select transfer time [Setup Setting Mode: Setting group No. 58 (
Sn58
)]
Parameter symbol
Data range
Factory set value
2 P V.T M
0.0 to 100.0 seconds
0.0
To display “PV select transfer time”, choose “Control with PV select” in Function
block No. 58: Select function for Input 2 (Engineering mode).
Select function for input 2 [Engineering mode: Function block No. 58 (
Fn58
)]
Parameter symbol
Data range
Factory set value
r
2 P V
0: No function
1: Remote setting input
2: 2-loop control/Differential temperature control
3: Control with PV select
4: Cascade control (Slave single
Cascade) *
5: Cascade control (Master single
Cascade) *
6: Input circuit error alarm
PID control: 0 to 6
Pressure/temperature control operation [MC-(V)COS(R)]: 0 to
2, 6
Heating/Cooling control: 0 to 3, 6
1
Refer to “4. Parameters that are Initialized/Modified when Setting is Changed”
for the parameters that are initialized or changed when the Select function for
input 2 is changed.
Selection of PV select trigger [Engineering mode: Function block No. 58 (
Fn58
)]
Parameter symbol
Data range
Factory set value
2 P V.T G
0: Switching by level
1: Switching by signal (Key, DI and Communication)
0
To display “Selection of PV select trigger”, choose “Control with PV select” in
Function block No. 58: Select function for Input 2 (Engineering mode).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...