172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
46
58
2.MCdb
Input 2_Deadband
1) 8)
★
0 to 10% of input_2 span
[Decimal point position depends on the
setting for Input 2_Valve coefficient F.]
See
Table 1
in 3.7.3
★
Data included in Memory area
1)
Displayed when "2-loop control/Differential temperature control" or "Cascade control" is selected in "Select function for Input 2."
2)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 2_Control action".
3)
Displayed when "Input 2_Proportional band [heat-side]" in the same memory area is other than 0 (0.0).
4)
Displayed when "Input 2_Proportional band [heat-side]" in any memory area is 0 (0.0). (Common setting in memory area)
5)
Displayed when "Input 2_Integral time [heat-side]" in the same memory area is other than 0 (0.0, 0.00).
6)
Displayed when "Input 2_Integral time [heat-side]" in the same memory area is 0 (0.0, 0.00).
7)
Displayed when Bottom suppression function is available.
8)
Displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 2_Control action".
3.7.5 Parameter group No. 56: Input 1_Cooling control (
1.COOL
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Pn56
Parameter group No. 56
1)
This is the first parameter symbol of
Parameter group No. 56
59
1. Pc
Input 1_Proportional band
[cool-side]
1) 2)
★
TC/RTD inputs:
1 (0.1, 0.01) to Input 1_Input span
(Unit:
C [
F])
(When Control with PV select: 1 to PV
select input span)
[Varies with the setting of the Decimal
point position.]
Voltage (V)/Current (I) inputs:
0.1 to 1000.0% of Input 1_Input span
(When Control with PV select: 0.1 to
1000.0 % of PV select input span)
TC/RTD
inputs: 30
V/I inputs:
3.0
60
1. Ic
Input 1_Integral time [cool-
side]
1) 2)
★
0 to 3600 seconds, 0.0 to 3600.0
seconds or 0.00 to 360.00 seconds
0 (0.0, 0.00): PD action
[Varies with the setting of the Integral/
Derivative time decimal point position.]
240
61
1. dc
Input 1_Derivative time
[cool-side]
1) 2)
★
0 to 3600 seconds, 0.0 to 3600.0
seconds or 0.00 to 360.00 seconds
0 (0.0, 0.00): PI action
[Varies with the setting of the Integral/
Derivative time decimal point position.]
60
62
1. db
Input
1_Overlap/Deadband
1)
★
TC/RTD inputs:
-(Input 1_Input span) to +(Input 1_
Input span)
(When Control with PV select:
-(PV select input span) to +(PV select
input span)
(Unit:
C [
F]))
[Varies with the setting of the Decimal
point position.]
Voltage (V)/Current (I) inputs:
-100.0 to +100.0% of Input 1_Input
span
(When Control with PV select:
-100.0 to +100.0% of PV select input
span)
Minus (-) setting results in Overlap.
However, the overlapping range is within
the proportional range.
TC/RTD
inputs: 0
V/I inputs:
0.0
63
1.oLHc
Input 1_Output limiter high
[cool-side]
1)
★
Input 1_Output limiter low [cool-side] to
105.0%
105.0
64
1.oLLc
Input 1_Output limiter low
[cool-side]
1)
★
-5.0% to Input 1_Output limiter high
[cool-side]
-5.0
★
Data included in Memory area
1)
Displayed when the “Input 1_Control action” is Heating/Cooling PID control.
2)
Displayed when the “Input 1_Proportional band [heat-side]” in the same memory area is other than 0 (0.0)
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...