172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
263
Remote/Local transfer state
The table below shows the actual Remote/Local modes and displays under different
combinations of settings by Key operation, Communication, and Digital input (DI).
Setting via front keys or
through communication
Setting via Digital Input (DI)
Instrument status
Remote mode
Remote mode
Remote mode
Local mode
Local mode
Local mode
Remote mode
Local mode
Parameter setting
Remote/Local transfer
[Operation Transfer Mode]
Parameter symbol
Data range
Factory set value
R/ L
When “Remote setting input” is selected at Select function for
input 2
LoC
: Local mode
rEM
: Remote mode
LoC
To display
“Remote/Local transfer”, choose “Remote setting input” in Function
block No. 58: Select function for Input 2 (Engineering mode).
Input 2_Input type [Engineering Mode: Function block No. 22 (
Fn22
)]
Parameter symbol
Data range
Factory set value
2. IN P
0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PL II
10: TC input U
11: TC input L
12: TC input PR40-20
13: RTD input Pt100
14: RTD input JPt100
15: Current input 0 to 20 mA DC
16: Current input 4 to 20 mA DC
17: Voltage input 0 to 10 V DC
18: Voltage input 0 to 5 V DC
19: Voltage input 1 to 5 V DC
20: Voltage input 0 to 1 V DC
21: Voltage input
10 to
10 V DC
22: Voltage input
5 to
5 V DC
23: Voltage input 0 to 100 mV DC
24: Voltage input 0 to 10 mV DC
Same as Input 1_Input
type
Input 2_Input type is not displayed when
“No function” is selected in Function
block No. 58: Select function for Input 2 (Engineering mode).
Refer to “4. Parameters that are Initialized/Modified when Setting is Changed” for
the parameters that are initialized or changed when the Input 2_input type is
changed.
Select function for input 2 [Engineering mode: Function block No. 58 (
Fn58
)]
Parameter symbol
Data range
Factory set value
r
2 P V
0: No function
1: Remote setting input
2: 2-loop control/Differential temperature control
3: Control with PV select
4: Cascade control (Slave single
Cascade) *
5: Cascade control (Master single
Cascade) *
6: Input circuit error alarm
PID control: 0 to 6
Pressure/temperature control operation [MC-(V)COS(R)]: 0 to
2, 6
Heating/Cooling control: 0 to 3, 6
1
Refer to “4. Parameters that are Initialized/Modified when Setting is Changed”
for the parameters that are initialized or changed when the Select function for
input 2 is changed.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...