172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
190
Event 3 differential gap [Engineering Mode: Function block No. 43 (
Fn43
)]
Parameter symbol
Data range
Factory set value
EH 3
Same as Event 1 differential gap
Deviation, Process and SV:
TC/RTD inputs: 2
V/I inputs: 0.2% of input
span
MV: 0.2
Event 4 differential gap [Engineering Mode: Function block No. 44 (
Fn44
)]
Parameter symbol
Data range
Factory set value
EH 4
Same as Event 1 differential gap
Deviation, Process and SV:
TC/RTD inputs: 2
V/I inputs: 0.2% of input
span
MV: 0.2
7.1.5 Preventing event from turning on due to a transient abnormal input
Event timer can be used to prevent event from turning on for the event state shorter
than the set time.
Description of function
When an event state becomes ON, the output is suppressed until the Event timer set
time elapses. If the event output is still ON after time is up, the output will resume. If
an event state is cancelled while the event timer is activated, no event output is
turned on.
Example: When the setting of Event 1 timer is 50.0 seconds
The Event timer is also activated for the following reasons:
When set to the event state simultaneously with power turned on
When set to the event state simultaneously with control changed to RUN
(control start) from STOP (control stop).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...