172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
257
Setting PID constant
PID control is employed as the control algorithm of temperature control of the MC-
COS(R)/MC-VCOS(R) series, therefore, the PID constant must be set for operation.
8.9 Controlling with Manual Control
To conduct the Manual control, you need to select the Manual mode using the
Auto/Manual transfer.
The Auto/Manual transfer can be made by a key operation, Digital input (DI) or
communication (optional).
Refer to the SC-F71 Instruction Manual [Host communication] (172-65711M)
for the Auto Manual transfer through communication.
Refer to 6.8 Suppressing Sudden Change in Output (Balanceless Bumpless)
for the Manipulated output value (balanceless bumpless) associated with the
Auto/Manual transfer.
Setting procedure
Selection by front key operation
Transfer Auto mode to Manual mode
Transfer Manual mode to Auto mode
During manual mode, the Manual (MAN) mode lamp is lit.
Refer to P. 8-59 for the Display position of the lamp.
R/S
RUN
1.
A/M
AUTO
setting mode
PV/SV monitor
Monitor & SV
1.A/M
MAN
2.A/M
AUTO
2.A/M
MAN
280
.
Operation transfer mode
Auto/Manual
transfer
Input 1_
In case of two inputs
(2 seconds
or more)
In case of
one input
0 0
.
Switch to Manual mode
Input 2_Auto/Manual transfer
MODE
RUN/STOP
transfer
MODE
or
MODE
or
MODE
+
MODE
+
setting mode
PV/MV monitor
Monitor & SV
280
.
50 0
.
(Several
times)
Switch to Manual mode
1.
A/M
MAN
1.A/M
AUTO
2.
A/M
MAN
2.A/M
AUTO
Auto/Manual Transfer
Input 1_
Auto/Manual Transfer
Input 2_
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...