13.
Fully open the sash and press
Mute
. This step sets the sash position sensor output,
10 V position.
14.
Set the sash to the lower position, for example, close and press
Mute
.
15.
Set the positions as required:
For 1 position operation:
When only the lower position is required (for example,
close only), press
↑
/
↓
together to quit.
For 2 position operation:
Set the sash to the normal working height (for
example, 500 mm) and press
Mute
.
Press
↑
/
↓
together to quit, when only 2 positions
(lower and middle) are required.
For 3 position operation:
Set the sash to the full opening height (for example,
750 mm) and press
Mute
.
The lower, middle and top positions are now
calibrated. Press
Mute
to quit calibration mode.
16.
Use the
↓
button and select
Back to Set up menu
, then press
Mute
.
17.
Use the
↓
button and select
Exit and Save Changes
, then press
Mute
.
18.
The controller now enters
Run
mode.
7.2.1
Calibration notes
The sash may slightly over-run past the calibration points, when the sash motor drive is
set to a fast speed. When calibrating the sash positions, allow a margin for the sash to
over-travel past the calibration height.
For example, before calibrating the lower position, fully close the sash and then open it
by 5 mm, or before calibrating the middle position, open the sash to the normal height
and then lower it by 5 mm.
7.3
Sash lock function
This section describes the calibration of the Auto Sash Controller from the
AFA4000/2/AS.
Note: Refer to section 7.4 to calibrate the Auto Sash Controller from the Auto Sash keypad
Summary of Contents for AFA4000/2
Page 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Page 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Page 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Page 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Page 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Page 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Page 127: ...AFA4000 2 Airflow Monitor p 127 ...
Page 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Page 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...