AFA4000/2
Airflow Monitor / p.169
Connector
Terminal Connection
Ratings &
Specification
BMS Output Relays
CN11,12,13,14
•
4 programmable volt-free
outputs
•
Change-over relays R1 -R4
3-way plug-in terminal
blocks
•
Max 30 Vac/dc 1 A
Analogue Outputs CN9
•
6-way plug-in terminal
block
•
0-10 Vdc over Sash Height
(2-way) (Programable 0-
10, 1-10,0-5,1-5V)
•
4-20mA over Sash Height
(2 Way) (Programable 0-
20 or 4-20 mA)
•
External Sounder (2-way)
•
0-10 V Max 10 V
(Current limited)
•
4-20 mA Max 24 V
•
Max 24 Vdc
100 mA (PTC Fused
200 mA)
BMS Digital Inputs CN10
•
4 programmable digital
inputs
•
8-way plug-in terminal
block
•
Max 24 Vdc
100 mA per input
•
Input impedance
100
kΩ
RS485 Comms (Optional)
•
Plug-in expansion module
•
8-way plug in terminal
block
•
Isolated RS485
output
15.2.4
Supply and field wiring requirements
Mains
5Supply
UK
3-pin single-gang socket or fused spur 3 A rated for 3-pin
plug
USA
2-pin single-gang socket or fused spur 3 A rated for 2-pin
plug
EURO
2-pin single-gang socket or fused spur 3 A rated for 2-pin
plug
Summary of Contents for AFA4000/2
Page 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Page 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Page 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Page 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Page 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Page 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Page 127: ...AFA4000 2 Airflow Monitor p 127 ...
Page 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Page 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...