AFA4000/2
Airflow Monitor / p.148
The sash will not open automatically if:
•
The sash beam is broken - object detected in the sash opening.
•
The controller does not detect sash movement when the motor is driving.
12.2.3.1
AFA4000/2/AS only
When the Auto open feature is enabled in the menu and is switched on from the keypad,
*
(asterix) is displayed in the left-hand corner of the Status Window, for example
* User
present
.
To enable Auto open, press and hold
Mute
. Then press and hold
↑
for 1 second or until
the
*
symbol displays.
To disable Auto open, press and hold
Mute.
Then press and hold
↑
for 1 second or until
the * symbol disappears.
12.2.4
Building Management System (BMS) inputs
The sash can be set to operate with the following BMS inputs:
Input
Description
Open/Close
Single start or end of day operation from BMS input.
The sash will only drive when the user is not present and the
sash beam is clear.
EV (Emergency)
Open/Close
Note: EV audible alarm tone will sound when the EV input is
active.
The sash will only drive if the user is not present and the
sash beam is clear. In EV mode the sash can be manually
moved when the user is detected. The sash will then auto
drive closed/open again, when the EV input is still active and
when the user is not detected.
Fire Alarm Close
Note: An audible alarm tone will sound whilst the fire alarm
input is active.
The sash will only drive when the user is not present and the
sash beam is clear. In Fire Alarm mode, the sash can be
manually moved if the user is detected. The sash will then
Summary of Contents for AFA4000/2
Page 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Page 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Page 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Page 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Page 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Page 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Page 127: ...AFA4000 2 Airflow Monitor p 127 ...
Page 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Page 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...