AFA4000/2
Airflow Monitor / p.33
•
When the Auto Open feature is enabled, the sash
automatically drives to the mid-position when the
user is present.
•
There is a time delay following user detection.
•
When the Auto Lock feature is enabled and a Sash
Lock position has been calibrated, the Auto Close
feature is disabled and the sash locks in its current
position when the sash is raised to the Sash Lock
position or higher. This facilitates loading the Fume
Cupboard.
Method C
–
3 Positions
•
The bottom, mid and top positions are calibrated.
•
The sash automatically drives to the bottom position,
when the user is not present.
•
Press the
Down
pushbutton to drive the sash to the
bottom position, when the user is present.
•
Press the
Up
pushbutton to drive the sash to the
next calibrated position, when the user is present.
•
When the Tiptronic feature is enabled, manually tip
the sash upwards and the sash will drive to the next
calibrated position.
•
Manually tip the sash downwards and the sash will
drive to the bottom position.
•
When the Auto Open feature is enabled, the user is
present and the sash is lower than the mid position,
the sash automatically drives to the mid-position.
•
There is a time delay following user detection.
•
When the Auto Lock feature is enabled and a Sash
Lock position has been calibrated, the Auto Close
feature is disabled and the sash locks in its current
position when the sash is raised to the Sash Lock
position or higher. This facilitates loading the Fume
Cupboard.
Summary of Contents for AFA4000/2
Page 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Page 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Page 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Page 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Page 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Page 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Page 127: ...AFA4000 2 Airflow Monitor p 127 ...
Page 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Page 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...