AFA4000/2
Airflow Monitor / p.159
When a BMS input is in an active condition, the current alarm displays in the status
window:
Alarm message
Description
Fire Alarm
This is displayed along with the normal text, for example
Fire
Alarm
or
User present,
when the fire alarm input is activated.
The sash will drive closed when the user is not detected and
the sash is clear. The sash can be operated manually when
the user is detected (auto open, tiptronic & pushbuttons are
disabled).
BMS open
This is displayed along with the normal text when the user is
not detected and when the BMS Open input is activated. The
sash will drive open when the user is not present and the
sash is clear. The sash can be operated normally when the
user is detected (auto open, tiptronic & pushbuttons are
active).
BMS close
This is displayed when the BMS Close input is activated, the
sash will drive closed when the user is not present and the
sash is clear. The sash can be operated normally when the
user is detected (auto open, tiptronic & pushbuttons are
active).
Emergency (up)
This is displayed along with the normal text when the user is
not detected and when the EV Open input is activated. The
sash will drive open when the user is not present and the
sash is clear. The sash can be operated manually when the
user is detected (auto open, tiptronic & pushbuttons are
disabled).
Emergency (dn)
This is displayed along with the normal text when the user is
not detected and when the EV Close input is activated. The
sash will drive closed when the user is not present and the
sash is clear. The sash can be operated manually when the
Summary of Contents for AFA4000/2
Page 1: ...AFA4000 2 Airflow monitor Installation and operating manual Issue 1 ...
Page 50: ...AFA4000 2 Airflow Monitor p 50 Figure 21 AFA4000 2 typical connection diagram ...
Page 51: ...AFA4000 2 Airflow Monitor p 51 Figure 22 AFA4000 2 AS typical connection diagram ...
Page 52: ...AFA4000 2 Airflow Monitor p 52 5 4 Dimensions Figure 23 AFA4000 2 and AFA4000 2 AS dimensions ...
Page 53: ...AFA4000 2 Airflow Monitor p 53 Figure 24 SM7 airflow sensor dimensions ...
Page 90: ...AFA4000 2 Airflow Monitor p 90 6 10 Auto Sash System Control Box general wiring diagram ...
Page 127: ...AFA4000 2 Airflow Monitor p 127 ...
Page 140: ...AFA4000 2 Airflow Monitor p 140 Figure 69 Typical connection diagram ...
Page 144: ...AFA4000 2 Airflow Monitor p 144 Figure 70 Connection diagram with RS232 485 converter ...