![background image](http://html.mh-extra.com/html/teco-westinghouse/eq7-series/eq7-series_instruction-manual_1072530163.webp)
4-94
The operation timings of each signal are shown below.
E31, E32
Frequency Detection (Level and Hysteresis width)
E36, E54 (Frequency Detection 2 and 3 (Level))
When the output frequency (estimated/detected speed) exceeds the frequency detection level specified by E31,
the "Frequency (speed) detected signal" comes ON; when it drops below the "Frequency detection level minus
Hysteresis width specified by E32," it goes OFF.
The following three settings are available.
Output signal
Data assigned
to output
terminal
Operation level
Hysteresis width
Range: 0.0 to 500.0
Hz
Range: 0.0 to 500.0
Hz
Frequency (speed)
detected signal
FDT
2
E31
E32
Frequency (speed)
detected signal 2
FDT2
31
E36
Frequency (speed)
detected signal 3
FDT3
58
E54