4-12
P codes: Motor 1 Parameters
Code
Name
Data setting range
C
ha
nge
w
hen
run
ning
D
a
ta
c
op
y
ing
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
P01 Motor 1
(No. of poles) 2 to 22 poles
N
Y1 Y2
4
Y
Y
Y
Y
4-109
P02
(Rated capacity) 0.01 to 1000 kW (when P99 = 0, 2, 3 or 4)
0.01 to 1000 HP (when P99 = 1)
N
Y1 Y2
*7
Y
Y
Y
Y
4-109
P03
(Rated current) 0.00 to 2000 A
N
Y1 Y2
*7
Y
Y
Y
Y
P04
(Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated
slip frequency)
2: Tune while the motor is rotating under V/f control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c")
3: Tune while the motor is rotating under vector
control
(%R1, %X, rated slip frequency, no-load current,
magnetic saturation factors 1 to 5, and magnetic
saturation extension factors "a" to "c." Available
when the vector control is enabled.)
N
N
0
Y
Y
Y
Y
4-110
P05
(Online tuning) 0: Disable 1: Enable
Y
Y
0
Y
N
N
N
4-111
P06
(No-load current) 0.00 to 2000 A
N
Y1 Y2
*7
Y
Y
Y
Y
P07
(%R1) 0.00% to 50.00%
Y
Y1 Y2
*7
Y
Y
Y
Y
P08
(%X) 0.00% to 50.00%
Y
Y1 Y2
*7
Y
Y
Y
Y
P09 (Slip compensation gain for
driving)
0.0% to 200.0%
Y*
Y
100.0
Y
Y
Y
N
4-112
P10 (Slip compensation response
time)
0.01 to 10.00 s
Y
Y1 Y2
0.12
Y
N
N
N
P11 (Slip compensation gain for
braking)
0.0% to 200.0%
Y*
Y
100.0
Y
Y
Y
N
P12 (Rated slip frequency)
0.00 to 15.00 Hz
N
Y1 Y2
*7
Y
Y
Y
N
P13 (Iron loss factor 1)
0.00% to 20.00%
Y
Y1 Y2
*7
Y
Y
Y
Y
P14 (Iron loss factor 2)
0.00% to 20.00%
Y
Y1 Y2
0.00
Y
Y
Y
Y
P15 (Iron loss factor 3)
0.00% to 20.00%
Y
Y1 Y2
0.00
Y
Y
Y
Y
P16 (Magnetic saturation factor 1)
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P17 (Magnetic saturation factor 2)
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P18 (Magnetic saturation factor 3)
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P19 (Magnetic saturation factor 4)
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P20 (Magnetic saturation factor 5)
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P21 (Magnetic saturation extension
factor "a")
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P22 (Magnetic saturation extension
factor "b")
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P23 (Magnetic saturation extension
factor "c")
0.0% to 300.0%
Y
Y1 Y2
*7
Y
Y
Y
Y
P53 (%X correction factor 1)
0% to 300%
Y
Y1 Y2
100
Y
Y
Y
Y
4-113
P54 (%X correction factor 2)
0% to 300%
Y
Y1 Y2
100
Y
Y
Y
Y
P55 (Torque current under vector
control)
0.00 to 2000 A
N
Y1 Y2
*7
N
Y
Y
Y
P56 (Induced voltage factor under
vector control)
50% to 100%
N
Y1 Y2 85 (90)
*8
N
Y
Y
Y
P57 Reserved *9
―
-
-
-
-
-
-
-
―
P99 Motor 1 Selection
0: Motor characteristics 0 (Reserved)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Reserved)
3: Motor characteristics 3 (Reserved)
4: Motor characteristics 1 (kW rating motors)
N
Y1 Y2
1
Y
Y
Y
Y
4-113
The shaded function code are applicable to the quick setup.
*7 The motor parameters are automatically set, depending upon the inverter's capacity. See Table B.
*8 85% for inverters of 150 HP or less; 90% for those of 175 HP or above.
*9 Factory use. Do not access these function codes.
The shaded function codes are applicable to the quick setup.
Y: Applicable / N: Not Applicable.