4-70
The LD/MD-mode inverter is subject to restrictions on the function code data setting range and internal processing
as listed below.
Function
codes
Name
Variable Torque Constant Torque
CT-Vector
Remarks
F21*
DC braking
(Braking level)
Setting range: 0 to 80%
Setting range:
0 to 100%
In the LD/MD mode, a
value out of the range, if
specified, automatically
changes to the maximum
value allowable in the LD
mode.
F26
Motor sound
(Carrier
frequency)
Setting range:
0.75 to 16 kHz
(0.5 to 30 HP)
0.75 to 10 kHz
(40 to 100 HP)
0.75 to 6 kHz
(125 to 900 HP)
0.75 to 4 kHz
(1000 HP)
Setting range:
0.75 to 2 kHz
(125 to 700 HP)
Setting range:
0.75 to 16 kHz
(0.5 to 125 HP)
0.75 to 10 kHz
(125 to 700 HP)
0.75 to 6 kHz
(800 and 900 HP)
F44
Current limiter
(Level)
Initial value:
130%
Initial value:
145%
Initial value: 160%
Switching the drive mode
with function code F80
automatically initializes the
F44 data to the value
specified at left.
F03*
Maximum
frequency
Setting range: 25 to 500 Hz
Upper limit: 120 Hz
Setting range:
25 to 500 Hz
Upper limit:
500 Hz
In the variable/constant
torque mode, if the
maximum frequency
exceeds 120 Hz, the
actual output frequency is
internally limited to 120 Hz.
―
Current
indication and
output
Based on the
rated current level
for variable
torque mode
Based on the
rated current level
for constant
torque mode
Based on the rated
current level for
CT-Vector mode
―
Even switching to the Variable/Constant Torque mode cannot automatically change the motor rated capacity
(P02*), so configure the P02* data to match the applied motor rating as required.