7-5
Set value
Frequency command
Run command (Run/Stop)
0
F01 / C30
F02
1
Enabled / RS485 (Port 1)
F02
2
F01 / C30
Enabled / RS485 (Port 1)
3
Enabled / RS485 (Port 1)
Enabled / RS485 (Port 1)
4
Enabled / RS485 (Port 2)
F02
5
Enabled / RS485 (Port 2)
Enabled / RS485 (Port 1)
6
F01 / C30
Enabled / RS485 (Port 2)
7
Enabled / RS485 (Port 1)
Enabled / RS485 (Port 2)
8
Enabled / RS485 (Port 2)
Enabled / RS485 (Port 2)
Command Register
EQ7 Drive Command Register: 1798 (Decimal)
Bit 0: Run Forward
Bit 1: Run Reverse
Bit 2 ~ Bit 15: Refer to the EQ7 Drive AC Drive Instruction Manual
Examples:
Run Forward Command (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 06 00 01 A9 7F
Run Reverse Command (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 06 00 02 E9 7E
Stop Command (EQ7 Drive Address: 01)
Command String (hexadecimal): 01 06 07 06 00 00 68 BF
Note:
The last 2 bytes of the command strings consist of a CRC16 checksum, please refer to the Refer to the EQ7
Communications Manual for additional information.
H30
Communications Link Function