4-13
H
codes
: High Performance Functions
Code
Name
Data setting range
C
ha
nge
w
hen
runnin
g
D
a
ta
c
op
y
in
g
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
H03 Data Initialization
0: Disable initialization
1: Initialize all function code data to the factory
defaults
2: Initialize motor 1 parameters
3: Initialize motor 2 parameters
N
N
0
Y
Y
Y
Y
*11
H04 Auto-reset
(Times) 0: Disable; 1 to 10
Y
Y
0
Y
Y
Y
Y
H05
(Reset interval) 0.5 to 20.0 s
Y
Y
5.0
Y
Y
Y
Y
H06 Cooling Fan ON/OFF Control
0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
Y
Y
0
Y
Y
Y
Y
H07 Acceleration/Deceleration
Pattern
0: Linear
1: S-curve (Weak)
2: S-curve (Arbitrary, according to H57 to H60 data)
3: Curvilinear
Y
Y
0
Y
Y
Y
N
H08 Rotational Direction Limitation
0: Disable
1: Enable (Reverse rotation inhibited)
2: Enable (Forward rotation inhibited)
N
Y
0
Y
Y
Y
N
H09 Starting Mode
(Auto search) 0: Disable
1: Enable (At restart after momentary power failure)
2: Enable (At restart after momentary power failure
and at normal start)
N
Y
0
Y
N
N
N
H11 Deceleration Mode
0: Normal deceleration
1:
Coast-to-stop
Y
Y
0
Y
Y
Y
N
H12 Instantaneous Overcurrent
Limiting
(Mode selection)
0: Disable
1: Enable
Y
Y
1
Y
N
N
N
H13 Restart Mode after Momentary
Power Failure
(Restart time)
0.1 to 20.0 s
Y
Y1 Y2
*10
Y
Y
Y
N
H14
(Frequency fall rate) 0.00: Deceleration time selected by F08,
0.01 to 100.00 Hz/s, 999: Follow the current limit
command
Y
Y
999
Y
Y
N
N
H15
(Continuous running level) 200 to 300 V for 230 V series
400 to 600 V for 460 V series
Y
Y2
235
470
Y
N
N
N
H16
(Allowable momentary power
failure time)
0.0 to 30.0 s
999: Automatically determined by inverter
Y
Y
999
Y
Y
Y
N
H18 Torque Control (Mode selection) 0: Disable (Speed control)
2: Enable (Torque current command)
3: Enable (Torque command)
N
Y
0
N
Y
Y
Y
H26 Thermistor (for motor)
(Mode selection)
0: Disable
1: PTC (The inverter immediately trips with
0h4
displayed.)
2: PTC (The inverter issues output signal
THM
and
continues to run.)
3: NTC (When connected)
Y
Y
0
Y
Y
Y
Y
H27
(Level) 0.00 to 5.00 V
Y
Y
0.35
Y
Y
Y
Y
H28 Droop Control
-60.0 to 0.0 Hz
Y
Y
0.0
Y
Y
Y
N
H30 Communications Link Function
(Mode selection)
Frequency command Run command
0: F01/C30
F02
1: RS-485 (Port 1)
F02
2: F01/C30
RS-485 (Port 1)
3: RS-485 (Port 1)
RS-485 (Port 1)
4: RS-485 (Port 2)
F02
5: RS-485 (Port 2)
RS-485 (Port 1)
6: F01/C30
RS-485 (Port 2)
7: RS-485 (Port 1)
RS-485 (Port 2)
8: RS-485 (Port 2)
RS-485 (Port 2)
Y
Y
0
Y
Y
Y
Y
H42 Capacitance of DC Link Bus
Capacitor
Indication for replacement of DC link bus capacitor
0 to 65535
Y
N
-
Y
Y
Y
Y
H43 Cumulative Run Time of Cooling
Fan
Indication for replacement of cooling fan
0 to 99990 hours
Y
N
-
Y
Y
Y
Y
H44 Startup Counter for Motor 1
Indication of cumulative startup count
0 to 65535 times
Y
N
-
Y
Y
Y
Y
H45 Mock Alarm
0: Disable
1: Enable (Once a mock alarm occurs, the data
automatically returns to 0.)
Y
N
0
Y
Y
Y
Y
H46 Starting Mode
(Auto search delay time 2)
0.1 to 20.0 s
Y
Y1 Y2
*7
Y
Y
N
Y
H47 Initial Capacitance of DC Link
Bus Capacitor
Indication for replacement of DC link bus capacitor
0 to 65535
Y
N
-
Y
Y
Y
Y
H48 Cumulative Run Time of
Capacitors on Printed Circuit
Boards
Indication for replacement of capacitors
0 to 99990 hours
(The cumulative run time can be modified or reset.)
Y
N
-
Y
Y
Y
Y
*7 The motor parameters are automatically set, depending upon the inverter's capacity. See Table B.
*10 The factory default differs depending upon the inverter's capacity. See Table A.
*11 Refer to the User Manual for detailed information on these parameters.
Y: Applicable / N: Not Applicable.