4-19
J codes: Application Functions 1
Code
Name
Data setting range
C
ha
nge
w
hen
runnin
g
D
a
ta
c
op
y
ing
Default
setting
Drive Control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
J01 PID Control
(Mode selection)
0: Disable
1: Enable (Process control, normal operation)
2: Enable (Process control, inverse operation)
3: Enable (Dancer control)
N
Y
0
Y
Y
Y
N
*11
J02
(Remote command SV)
0:
/
keys on keypad
1: PID command 1
(Analog input terminals [12], [C1], and [V2])
3: UP/DOWN
4: Command via communications link
N
Y
0
Y
Y
Y
N
J03
P (Gain)
0.000 to 30.000 times
Y
Y
0.100
Y
Y
Y
N
J04
I (Integral time)
0.0 to 3600.0 s
Y
Y
0.0
Y
Y
Y
N
J05
D (Differential time)
0.00 to 600.00 s
Y
Y
0.00
Y
Y
Y
N
J06
(Feedback filter)
0.0 to 900.0 s
Y
Y
0.5
Y
Y
Y
N
J08 (Pressurization starting frequency)
0.0 to 500.0 Hz
Y
Y
0.0
Y
Y
Y
N
J09
(Pressurizing time)
0 to 60 s
Y
Y
0
Y
Y
Y
N
J10
(Anti reset windup)
0% to 200%
Y
Y
200
Y
Y
Y
N
J11
(Select alarm output)
0: Absolute-value alarm
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm (with Latch)
7: Deviation alarm (with Hold and Latch)
Y
Y
0
Y
Y
Y
N
J12
(Upper level alarm (AH))
-100% to 100%
Y
Y
100
Y
Y
Y
N
J13
(Lower level alarm (AL))
-100% to 100%
Y
Y
0
Y
Y
Y
N
J15 (Stop frequency for slow flowrate)
0.0: Disable; 1.0 to 500.0 Hz
Y
Y
0.0
Y
Y
Y
N
J16 (Slow flowrate level stop latency)
0 to 60 s
Y
Y
30
Y
Y
Y
N
J17
(Starting frequency)
0.0 to 500.0 Hz
Y
Y
0.0
Y
Y
Y
N
J18 (Upper limit of PID process output)
-150% to 150%; 999: Depends on setting of F15
Y
Y
999
Y
Y
Y
N
J19 (Lower limit of PID process output)
-150% to 150%; 999: Depends on setting of F16
Y
Y
999
Y
Y
Y
N
J21 Dew Condensation Prevention
(Duty)
1% to 50%
Y
Y
1
Y
Y
Y
Y
J22 Commercial Power Switching
Sequence
0: Keep inverter operation (Stop due to alarm)
1: Automatically
switch
to
commercial-power
operation
N
Y
0
Y
N
N
Y
J56 PID Control(Speed command filter)
0.00 to 5.00 s
Y
Y
0.10
Y
Y
Y
N
J57
(Dancer reference position)
-100% to 0% to 100%
Y
Y
0
Y
Y
Y
N
J58
(Detection width of dancer
position deviation)
0: Disable switching PID constant
1% to 100% (Manually set value)
Y
Y
0
Y
Y
Y
N
J59
P (Gain) 2
0.000 to 30.000 times
Y
Y
0.100
Y
Y
Y
N
J60
I (Integral time) 2
0.0 to 3600.0 s
Y
Y
0.0
Y
Y
Y
N
J61
D (Differential time) 2
0.00 to 600.00 s
Y
Y
0.00
Y
Y
Y
N
J62
(PID control block selection)
0 to 3
bit 0: PID output polarity
0: Plus (add), 1: Minus (subtract)
bit 1: Select compensation factor for PID output
0 = Ratio (relative to the main setting)
1 = Speed command (relative to maximum
frequency)
N
Y
0
Y
Y
Y
N
J68 Brake Signal(Brake-OFF current)
0% to 300%
Y
Y
100
Y
Y
Y
N
J69 (Brake-OFF frequency/speed)
0.0 to 25.0 Hz
Y
Y
1.0
Y
N
N
N
J70
(Brake-OFF timer)
0.0 to 5.0 s
Y
Y
1.0
Y
Y
Y
N
J71
(Brake-ON frequency/speed)
0.0 to 25.0 Hz
Y
Y
1.0
Y
N
N
N
J72
(Brake-ON timer)
0.0 to 5.0 s
Y
Y
1.0
Y
Y
Y
N
J95
(Brake-OFF torque)
0% to 300%
Y
Y
100
N
Y
Y
N
J96
(Speed condition selection
0 to 31
N
Y
0
(Braking conditions))
Bit 0:
Criterion speed for brake-ON
(0: Detected speed, 1: Reference speed)
N
Y
Y
N
Bit 1:
Reserved.
N
N
N
N
Bit 2:
Response for brake-OFF current
(0: Slow response, 1: Quick response)
Y
Y
Y
N
Bit 3:
Criterion frequency for brake-ON
(0: Stop frequency (F25),
1: Brake-ON frequency (J71)
N
Y
Y
N
Bit 4:
Output condition of brake signal
(0: Independent of a run command ON/OFF
1: Only when a run command is OFF)
N
Y
Y
N
J97 Servo-lock
(Gain)
0.00 to 10.00 times
Y*
Y
0.10
N
N
Y
N
J98
(Completion timer)
0.000 to 1.000 s
Y
Y
0.100
N
N
Y
N
J99
(Completion range)
0 to 9999 pulses
Y
Y
10
N
N
Y
N
Y: Applicable / N: Not Applicable.