8-1
Chapter 8 Motor and Application Specific Settings
It is essential that before running the motor, the motor nameplate data matches the motor data in the EQ7 drive.
8.1 Set Motor Name Plate Data (P02, P03, F11)
The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data matches the
motor rated capacity shown in parameter P02. The setting should only be changed when driving a motor with a
different capacity.
Range:
0.01 to 1000 HP
To set parameter P02:
- Press
PRG
key, next select
QUICK SET or DATA SET
with
UP/DOWN
and
keys and press the
FUNC/DATA
key.
- In the parameter list move cursor to P02 with
UP/DOWN
keys and press
FUNC/DATA
key to select.
Note:
For kW rating motor set P99 to 4.
Default values vary based on the EQ7 drive model.
The motor rated current is set at the factory based on the EQ7 drive model. Enter the motor rated current from the
motor nameplate if it does not match the value shown in parameter P3.
This function sets the rated current value of motor 1.
Setting range:
0.00 to 2,000A
To set parameter P03:
- Press
PRG
key, next select
QUICK SET or DATA SET
with
UP/DOWN
and
keys and press the
FUNC/DATA
key.
- In the parameter list move cursor to P03 with
UP/DOWN
keys and press
FUNC/DATA
key to select.
This function sets the operation current level for the electronic thermal O/L. Verify that the motor FLA on the motor
nameplate matches the overload level shown in parameter F11
Setting range:
1 to 135% of the rated current of the inverter.
To set parameter F11:
- Press
PRG
key, next select
QUICK SET or DATA SET
with
UP/DOWN
and
keys and press the
FUNC/DATA
key.
- In the parameter list move cursor to F11 with
UP/DOWN
keys and press
FUNC/DATA
key to select.
P03
Motor 1 (Rated Current)
P02
Motor 1 (Capacity)
F11
Overload Detection Level