4-86
k
×
speed
Rated
×
voltage
Rated
×
2
]
5[
-
ltage
Battery vo
operation
battery
during
ramp)
-
(pre
speed
Reference
V
Figure C: Fan Power Supply Switching Connector
About battery operation (when
BATRY
is ON)
(1) The undervoltage protective function (
lu
) is deactivated.
(2) The inverter can run the motor even under an undervoltage condition.
(3) The
RDY
("Inverter ready to run") output signal is forcedly turned OFF.
(4) The bypass circuit of the charging resistor comes to be closed (73X ON) after a delay of time T1 from when the
BATRY
is turned ON. Further, after a delay of time T2 (a maximum of 0.1 second), the battery operation starts. For
the specifications of T1, see the table below.
Battery Operation Timing Diagram
T1 from
BATRY
ON to 73X ON
Power condition
30 kW / 50 HP
or below
37 kW / 60 HP
or above
After the control power supply goes OFF, the
battery power and control power are turned ON.
100 ms
500 ms
The control power remains ON or after a
momentary power failure happens.
205 ms
(5) The S-curve acceleration/deceleration is disabled.
(6) The battery operation speed can be calculated by the following formula.
.
Where,
Battery voltage: 24 VDC or higher for 200 V class series / 230 V class series for USA
48 VDC or higher for 400 V class series / 460 V class series for USA.
Rated speed : F04
Rated voltage : F05 (Motor rated voltage (V))
Safety coefficient (Less than 1, about 0.8
When using R1 and T1 (BATRY operation)
Setting
CN R (Red)
Usage
CN W (White)
CN W (White)
When not using R1 or T1
(Factory default)
CN R (Red)
Main power
MC1
BATRY
MC2
73X
Battery power supply
DC link bus voltage Edc
Run command
Detected speed
Undervoltage level
Reference Frequency
T1
T2
Battery operation-
enabled zone
ON
ON
ON
ON
ON
ON
ON
ON
S-curve acce./dece. disabled
0
LU
ON
RDY
ON