4.2.2 E codes (Extension Terminal Functions)
E01 to E07 Terminal [X1] to [X7] Function
E98 (Terminal [FWD] Function)
E99 (Terminal [REV] Function)
E01 to E07, E98 and E99 assign commands (listed below) to general-purpose, programming, digital input
terminals, [X1] to [X7], [FWD], and [REV].
These function codes can also switch the logic system between normal and negative to define how the inverter
logic interprets the ON or OFF state of each terminal. The factory default setting is normal logic system "Active
ON." So, descriptions that follow are given in normal logic system. They are, in principle, arranged in the numerical
order of assigned data. However, highly relevant signals are collectively described where one of them first
appears. Refer to the function codes in the "Related function codes" column, if any.
The EQ7 runs under "V/f control," "dynamic torque control," "vector control without speed sensor," or "vector
control with speed sensor." Some terminal commands assigned apply exclusively to the specific drive control,
which is indicated by letters Y (Applicable) and N (Not applicable) in the "Drive control" column in the table given
below. (Refer to page 4-2.)
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward"
FWD
), stop commands (e.g., "Coast to a stop"
BX
), and frequency
change commands can be assigned to digital input terminals. Depending upon the assignment states of
those terminals, modifying the function code setting may cause a sudden motor start or an abrupt change in
speed.
• When the inverter is controlled with the digital input signals, switching run or frequency command sources
with the related terminal commands (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
, and
LE
) may cause a
sudden motor start or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Terminal commands assigned
Symbol
Drive control
Related
function codes
Active ON Active OFF
V/f
w/o
PG
w/
PG
Torque
control
0
1000
Select multi-frequency (0 to 15 steps)
SS1
Y
Y
Y
N
C05 to C19
1
1001
SS2
Y
Y
Y
N
2
1002
SS4
Y
Y
Y
N
3
1003
SS8
Y
Y
Y
N
4
1004
Select ACC/DEC time (2 steps)
RT1
Y
Y
Y
N
F07, F08,
E10 to E15
5
1005
Select ACC/DEC time (4 steps)
RT2
Y
Y
Y
N
6
1006
Enable 3-wire operation
HLD
Y
Y
Y
Y
F02
7
1007
Coast to a stop
BX
Y
Y
Y
Y
8
1008
Reset alarm
RST
Y
Y
Y
Y
1009
9
Enable external alarm trip
THR
Y
Y
Y
Y
10
1010
Ready for jogging
JOG
Y
Y
Y
N
C20, H54, H55,
d09 to d13
11
1011
Select frequency command 2/1
Hz2/Hz1
Y
Y
Y
N
F01, C30
12
1012
Select motor 2
M2
Y
Y
Y
Y
A42
13
Enable DC braking
DCBRK
Y
Y
Y
N
F20 to F22
14
1014
Select torque limiter level 2/1
TL2/TL1
Y
Y
Y
Y
F40, F41, E16,
E17
15
Switch to commercial power (50 Hz)
SW50
Y
N
N
N
16
Switch to commercial power (60 Hz)
SW60
Y
N
N
N
17
1017
UP (Increase output frequency)
UP
Y
Y
Y
N
Frequency
command:
F01, C30
PID command:
J02
18
1018
DOWN (Decrease output frequency)
DOWN
Y
Y
Y
N
19
1019
Enable data change with keypad
WE-KP
Y
Y
Y
Y
F00
20
1020
Cancel PID control
Hz/PID
Y
Y
Y
N
J01 to J19,
J56 to J62
21
1021
Switch normal/inverse operation
IVS
Y
Y
Y
N
C53, J01