11-5
VT mode designed for variable torque load applications
Item
Specifications
Model EQ7-4XXX-C
0P5
001
002
003
005
007
010
015
020
025
030
040
050
060
075
100
-
-
*1
Nominal applied motor
for
three
phase input [HP]
1/2
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
-
-
*1
Nominal applied motor
for
single
phase input [HP]
1/4
1/2
1
1.5
3
3
5
7.5
10
10
15
20
25
30
30
40
-
-
Ou
tp
ut
r
at
in
gs
Three
phase
input
Rated capacity
*2
[kVA]
1.2
2.0
3.2
4.4
7.2
11
13.1 18.3
24
29
36
48
60
73
89
120
-
-
Rated current [A]
1.5
2.5
4
5.5
9
13.5 16.5
23
30.5
37
45
60
75
91
112
150
-
-
Single
phase
input
Rated capacity
*2
[kVA]
0.8
1.2
2.0
2.4
4.5
6.4
8.8
12
14
16
18
23
30
37
43
47
-
-
Rated current [A]
0.9
1.5
2.4
3.0
5.6
8.0
11
15
17
20
23
29
37
46
54
59
-
-
Rated voltage
*3
[V]
Three-phase, 380 to 480 V (with AVR function)
Overload capability
150% -1 min, 200% -3.0 s
120% -1 min
Input
r
at
in
gs
Three
phase
input
Voltage, frequency
Three-phase, 380 to 480 V, 50/60 Hz
Voltage, frequency
variations
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less)
*4
, Frequency: +5 to -5%
Input current with
DCR
0.7
1.5
2.6
4
6.6
9.2
12.5 18.8 25.1 31.3 36.3 50.2 60.2 72.7 89.1
120
-
-
Input current without
DCR
1.4
2.6
5.1
7.1
11.3
15
20.1 28.6
38
45.4 52.6 67.7
82
99.1
121
-
-
-
Required capacity
with DCR
*5
[kVA]
0.6
1.2
2.2
3.1
5.2
7.4
10
15
20
25
29
40
48
58
71
96
-
-
Single
phase
input
Voltage, frequency
Single-phase, 380 to 480 V, 50/60 Hz
Voltage, frequency
variations
Voltage: +10 to -10% , Frequency: +5 to -5%
Input current with
DCR
1.0
1.8
3.5
4.7
8.5
11.7 15.7
24
28.6 34.6
40
53.4 69.1 84.3 99.7
110
-
-
Input current without
DCR
1.7
3.1
5.9
8.2
13.0 17.3 23.2
33
43.8 52.3 60.6 77.9 94.3
114
134
-
-
-
Required capacity
with DCR
*5
[kVA]
0.5
0.9
1.7
2.2
4.0
5.4
7.3
11
13
16
18
25
32
39
46
51
-
-
B
ra
kin
g
Torque
*6
[%]
150%
100%
70%
15%
7 to 12%
-
-
Braking transistor
Built-in
-
-
-
Built-in braking resister
Built-in
Braking time [s]
5 s
3.7s 3.7s 3.4s
%ED
5
3
5
3
2
2.2
2.2
1.4
DC reactor (DCR)
Option
As standard *7
Keypad
Multi-function keypad as standard
Applicable safety standards
UL508C, C22.2No.14, EN61800-5-1:2007,EN61800-5-2:2007 SIL2,
EN ISO13849-1:2008 PL=d Cat.3,EN954-1:1996 Cat.3
Enclosure (IEC60529)
IP20, UL open type , NEMA1(Option)
IP00 UL open type , NEMA1(Option)
Cooling method
Natural cooling
Fan cooling
Weight/Mass [lbs(kg)]
3.8
(1.7)
4.4
(2.0)
5.7
(2.6)
6.0
(2.7)
6.6
(3.0)
14.3
(6.5)
14.3
(6.5)
14.3
(6.5)
12.8
(5.8)
20.9
(9.5)
20.9
(9.5)
22
(10)
55.1
(25)
57.3
(26)
68.3
(31)
72.8
(33)
-
-
(*1) 4-pole standard motor
(*2) Rated capacity is calculated by assuming the output rated voltage as 230 V for 230 V series and 460 V for 460 V series.
(*3) Output voltage cannot exceed the power supply voltage.
(*4) Voltage unbalance [%] = (Max. voltage [V] - Min. voltage [V])/Three-phase average voltage [V] ×67(See IEC61800-3.) If this value is 2 to 3%, use an optional AC reactor (ACR).
(*5) Required when a DC reactor (DCR) is used.
(*6) Without external braking resistor condition. Average braking torque obtained by use of a motor. (Varies with the efficiency of the motor.)
(*7) For inverters of 100HP or above, the DC reactor is provided as separate standard component. Be sure to connect it to those inverters.