4-9
Code
Name
Data setting range
C
ha
nge
w
hen
run
ning
D
a
ta
c
op
y
ing
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control w/
PG
Torque
control
w/o
PG
E50 Coefficient for Speed Indication 0.01 to 200.00
Y
Y
30.00
Y
Y
Y
Y
4-100
E51 Display Coefficient for Input
Watt-hour Data
0.000 (Cancel/reset), 0.001 to 9999
Y
Y
0.010
Y
Y
Y
Y
E54 Frequency Detection 3 (Level) 0.0 to 500.0 Hz
Y
Y
60.0
Y
Y
Y
Y
4-101
4-94
E55 Current Detection 3
(Level) 0.00 (Disable);
Current value of 1% to 200% of the inverter rated
current
Y
Y1 Y2
*2
Y
Y
Y
Y
4-101
4-95
E56
(Timer) 0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
4-102
E61 Terminal [12] Extended Function 0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID command 1
5: PID feedback amount
6: Ratio setting
7: Analog torque limit value A
8: Analog torque limit value B
10:Torque command
11: Torque current command
17: Speed limit FWD
18: Speed limit REV
20: Analog input monitor
N
Y
0
Y
Y
Y
Y
E62 Terminal
[C1]
Extended
Function
N
Y
0
Y
Y
Y
Y
E63 Terminal
[V2]
Extended
Function
N
Y
0
Y
Y
Y
Y
E64 Saving of Digital Reference
Frequency
0: Automatic saving (when main power is turned OFF)
1: Saving by pressing
key
Y
Y
1
Y
Y
Y
Y
4-103
E65 Reference Loss Detection
(Continuous running frequency)
0: Decelerate to stop, 20% to 120%, 999: Disable
Y
Y
999
Y
Y
Y
Y
E78 Torque Detection 1
(Level) 0% to 300%
Y
Y
100
Y
Y
Y
Y
4-104
E79
(Timer) 0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
E80 Torque Detection 2/
Low Torque Detection
(Level)
0% to 300%
Y
Y
20
Y
Y
Y
Y
E81
(Timer) 0.01 to 600.00 s
Y
Y
20.00
Y
Y
Y
Y
Selecting function code data assigns the corresponding
function to terminals [FWD] and [REV] as listed below.
4-71
4-104
E98 Terminal [FWD] Function
0 (1000): Select multi-frequency (0 to 1 steps)
(
SS1
)
N
Y
98
Y
Y
Y
N
E99 Terminal [REV] Function
1 (1001): Select multi-frequency (0 to 3 steps)
(
SS2
)
N
Y
99
Y
Y
Y
N
2 (1002): Select multi-frequency (0 to 7 steps)
(
SS4
)
Y
Y
Y
N
3 (1003): Select multi-frequency (0 to 15 steps) (
SS8
)
Y
Y
Y
N
4 (1004): Select ACC/DEC time (2 steps)
(
RT1
)
Y
Y
Y
N
5 (1005): Select ACC/DEC time (4 steps)
(
RT2
)
Y
Y
Y
N
6 (1006): Enable 3-wire operation
(
HLD
)
Y
Y
Y
Y
7 (1007): Coast to a stop
(
BX
)
Y
Y
Y
Y
8 (1008): Reset alarm
(
RST
)
Y
Y
Y
Y
9 (1009): Enable external alarm trip
(
THR
)
(9 = Active OFF, 1009 = Active ON)
Y
Y
Y
Y
10 (1010): Ready for jogging
(
JOG
)
Y
Y
Y
N
11 (1011): Select frequency command 2/1
(
Hz2/Hz1
)
Y
Y
Y
N
12 (1012): Select motor 2
(
M2
)
Y
Y
Y
Y
13: Enable DC braking
(
DCBRK
)
Y
Y
Y
N
14 (1014): Select torque limiter level 2/1
(
TL2/TL1
)
Y
Y
Y
Y
15: Switch to commercial power (50 Hz)
(
SW50
)
Y
N
N
N
16: Switch to commercial power (60 Hz)
(
SW60
)
Y
N
N
N
17 (1017): UP (Increase output frequency)
(
UP
)
Y
Y
Y
N
18 (1018): DOWN (Decrease output frequency)
(
DOWN
)
Y
Y
Y
N
19 (1019): Enable data change with keypad (
WE-KP
)
Y
Y
Y
Y
20 (1020): Cancel PID control
(
Hz/PID
)
Y
Y
Y
N
21 (1021): Switch normal/inverse operation
(
IVS
)
Y
Y
Y
N
22 (1022): Interlock
(
IL
)
Y
Y
Y
Y
23 (1023): Cancel torque control
(
Hz/TRQ
)
N
N
N
Y
24 (1024): Enable communications link via RS-485
or fieldbus
(
LE
)
Y
Y
Y
Y
25 (1025): Universal DI
(
U-DI
)
Y
Y
Y
Y
26 (1026): Enable auto search for idling motor
speed at starting
(
STM
)
Y
Y
N
Y
The shaded function codes are applicable to the quick setup.
*2 The motor rated current is automatically set. See Table B (P03/A17).
Item values in parentheses indicated value for negative logic.
Y: Applicable / N: Not Applicable.