8-6
8.5 Reset EQ7 back to Factory Default
Parameter H03
Data Initialization
H03 initializes the current function code data to the factory defaults or initializes the motor parameters.
To change the H03 data, it is necessary to press the
+
keys or
+
keys (simultaneous keying).
Data for H03
Function
0
Disable initialization (Settings manually made by the user will be retained.)
1
Initialize all function code data to the factory defaults
2
Initialize motor 1 parameters in accordance with P02 (Rated capacity) and P99 (Motor 1
selection)
3
Initialize motor 2 parameters in accordance with A16 (Rated capacity) and A39 (Motor 2
selection)
• To initialize the motor parameters, set the related function codes as follows.
Step
Item
Action
Function code
1st motor
2nd motor
(1)
Motor
selection
Selects the motor
type
P99
A39
(2)
Motor
(rated
capacity)
Sets the motor
capacity (HP)
P02
A16
(3)
Data
initialization
Initialize motor
parameters
H03 = 2
H03 = 3
Function code data
to be initialized
If "Data = 0, 1, 3, or
4" in Step (1)
P01, P03, P06 to P23,
P53 to P56,H46
A15, A17, A20 to A37,
A53 to A56
If "Data = 2" in Step
(1), function codes
listed at the right are
also initialized
F04, F05
A02, A03
• Upon completion of the initialization, the H03 data reverts to "0" (factory default).
• If P02 or A16 data is set to a value other than the nominal applied motor rating, data initialization with H03
internally converts the specified value forcibly to the standard nominal applied motor rating. (Refer to Table B in
Section 4.1 "Function Code Tables.")
• Motor parameters to be initialized are for motors listed below under V/f control. When the base frequency,
rated voltage, and the number of poles are different from those of the listed motors, or when non-standard
motors are used, change the rated current data to that printed on the motor nameplate.
Motor selection
V/f control data
Data = 1
TWMC HP rating motors
4 poles 230 V/60 Hz, 460 V/60 Hz
Data = 2
Consult Factory
4 poles
―/50 Hz,
―/50 Hz
Data = 0 or 4
Consult Factory
4 poles 200 V/50 Hz, 400 V/50 Hz
Data = 3
Consult Factory
4 poles 200 V/50 Hz, 400 V/50 Hz
When accessing function code P02 with the keypad, take into account that P02 data automatically
updates data of function codes P03, P06 through P23, P53 through P56, and H46. Also, when accessing
function code A16, data of related function codes for each are automatically updated.