6-1
Chapter 6 Speed Reference Command Configuration
The EQ7 Drive offers users several choices to set the speed reference source. The most commonly used methods
are described in the next sections.
Frequency reference command is selected with parameter F01.
This function sets the frequency command source.
Setting Range:
0 to 12
To set parameter F01:
- Press
PRG
key, next select
QUICK SET or DATA SET
with
UP/DOWN
and
keys and press the
FUNC/DATA
key.
- In the parameter list move cursor to F01 with
UP/DOWN
keys and press
FUNC/DATA
key to select.
Data for F01
Function
0
Enable / keys on the keypad.
1
Enable the voltage input to terminal [12] (0 to
10 VDC, maximum frequency obtained at
10
VDC).
2
Enable the current input to terminal [C1] (0 to +20mA, +4 to +20 mA DC, maximum frequency
obtained at +20 mA DC). (SW5 on the control PCB should be turned to the C1 side (factory
default).
3
Enable the sum of voltage (0 to
10 VDC) and current inputs (+4 to +20 mA DC) given to
terminals [12] and [C1], respectively. See the two items listed above for the setting range and the
value required for maximum frequencies. (SW5 on the control PCB should be turned to the C1
side (factory default).)
Note: If the sum exceeds the maximum frequency (F03), the maximum frequency will apply.
5
Enable the voltage input to terminal [V2] (-10 to ±10 VDC, maximum frequency obtained at ±10
VDC).
7
Enable
UP
and
DOWN
commands assigned to the digital input terminals.
The
UP
command (any of E01 to E07 = 17) and
DOWN
command (any of E01 to E07 = 18)
should be assigned to any of digital input terminals [X1] to [X7].
For details, refer to the descriptions of E01 through E07.
8
Enable / keys on the keypad (balanceless-bumpless switching available).
11
Enable a digital input interface card (option).
(For details, refer to the Digital Input Interface Card Instruction Manual.)
12
Enable the "Pulse train input"
PIN
command assigned to digital input terminal [X7]
(E07 = 48), or a PG interface card (option).
6.1 Reference from Keypad (Default Setting, F01 = 0)
Speed reference from digital operator (Keypad) is the default setting. Use the
and
keys to change the speed
reference.
F01
Frequency Command 1