9-4
9.3 Setpoint Scaling / Transducer Feedback Scaling (E40, E41)
Use parameter E40 and E41 to scale the EQ7 set-point to the transducer connected. Parameter E40 has to be
programmed to the maximum range of the transducer and E41 to the minimum range of the transducer.
To set parameter E40, E41
- Press
PRG
key, next select
QUICK SET or DATA SET
with
UP/DOWN
and
keys and press the
FUNC/DATA
key.
- In the parameter list move cursor to E40, E41 with
UP/DOWN
keys and press
FUNC/DATA
key to select.
Example 1:
Example 2:
Transducer range: 0
– 150 PSI
Transducer range: 0
– 80 PSI
E40 = 150.00
E40 = 80.00
E41 = 0.00 (default)
E41 = 0.00 (default)
Use the
and
key to set the PID setpoint value
(E.g. 80.00 PSI)
Refer to the chapter 6 of the Instruction Manual for the preferred command (Run/Stop) method selection.