4-98
E43
LED Monitor (Item selection)
E48 (LED Monitor (Speed monitor item))
E43 specifies the running status item to be monitored and displayed on the LED monitor.
Specifying the speed monitor with E43 provides a choice of speed-monitoring formats selectable with E48 (LED
Monitor).
Monitor item
Display sample
on the LED
monitor
Unit
Meaning of displayed value
Function
code data
for E43
Speed monitor
Function code E48 specifies what to be displayed on the LED monitor.
0
Output frequency 1
(before slip
compensation)
Hz
Frequency actually being output
(E48 = 0)
Output frequency 2
(after slip
compensation)
Hz
Frequency actually being output
(E48 = 1)
Reference
frequency
Hz
Reference frequency being specified
(E48 = 2)
Motor speed
r/min
Output frequency (Hz) x
120
P01
(E48 = 3)
Load shaft
speed
r/min
Output frequency (Hz)
E50
(E48 = 4)
Line speed
m/min
Output frequency (Hz)
E50
(E48 = 5)
Display speed (%)
%
Output frequency
x 100
Maximum frequency
(E48 = 7)
Output current
A
Current output from the inverter in RMS
3
Output voltage
V
Voltage output from the inverter in RMS
4
Calculated torque
%
Motor output torque in %
(Calculated value)
8
Input power
kW
Input power to the inverter
9
PID command
-
PID command/feedback amount
transformed to that of virtual physical value
of the object to be controlled (e.g.
temperature)
Refer to function codes E40 and E41 for
details.
10
PID feedback
amount
-
12
PID output
%
PID output in % as the maximum frequency
being at 100%
14
Load factor
%
Load factor of the motor in % as the rated
output being at 100%
15
Motor output
kW
Motor output in kW
16
Analog input
-
An analog input to the inverter in a format
suitable for a desired scale.
Refer to function codes E40 and E41 for
details.
17
Torque current
%
Torque current command value or
calculated torque current
23
Magnetic flux
command
%
Magnetic flux command value
(Available only under vector control)
24
Input watt-hour
kWh
Input watt-hour (kWh)
100
25