4-84
3) Sequence with an emergency switching function --Part 2 (Automatic switching by the alarm output issued by
the inverter)
Servo-lock command --
LOCK
(Function code data = 47)
Turning this terminal command ON enables a servo-lock command; turning it OFF disables a servo-lock
command.
Refer to J97 through J99.
Pulse train input --
PIN
(Function code data = 48)
Pulse train sign --
SIGN
(Function code data = 49)
Assigning the command
PIN
to digital input terminal [X7] enables the frequency command by the pulse train input.
Assigning the command
SIGN
to one of the digital input terminals except [X7] enables the pulse train sign input to
specify the polarity of frequency command.
Refer to F01.