System typical application and adjustment NICE3000 User Manual
170
The setting of the highest, lowest and service floor
When two lifts are in parallel, if the floor structure is different, the F6-01 setting of
the lowest floor should be the same with the external call dial code of the corresponding lift
’
s
lowest floor. The setting of the highest floor should be the same with the corresponding physical
floor
’
s floor number of the highest floor
’
s external call dial code.
Following the principles mentioned above, the lift
’
s corresponding setting in the example
should be:
No.1 lift F6-00=4 6-01=1, No.2 lift F6-00=5 F6-01=2
3. The setting of service floor
As the instruction in 1, the Floor 2 of the No.2 lift in the example has the leveling plate but no
floor door, so it is no service floor, and needs to set service floor F6-05=65533.
7.6 Instruction of group control program
Details refer to the instruction of group control
7.7 Instruction of overload and full load
In order to facilitate the use of different users, NICE 3000 integrated controller supplies three
over load and full load signals inputting mode to fulfill these functions. When in use, correctly
set the corresponding parameters to avoid miss-operation. Briefly explain its use in the
following:
7.7.1 Car top switch
’
s terminal inputting mode:
When F5-36 is setting as 1, select car top switch inputting mode to fulfill over load.
The car top board of NICE 3000 (MCTC-CTB-A) has 8 switch inputting terminals (CN3). Among
those, the corresponding function of X7 terminal is full load signal, and that of X8 is over load
signal. The properties of these inputting terminals are defined by function code (F5-25). If the
F5-25
’
s parameter BIT6=1, the car top board signal X7 is N.O.; If the F5-25
’
s parameter
BIT6=0, the car top board signal X7 is N.C. The properties of over load signal X8 are the same.
Relationship is as follows, and the
“
X
”
in the following chart means any number:
Over load switch
’
s
property
F5-25 correct
parameters setting
Car top board X8
terminal
’
s inputting
voltage (V)
NICE 3000 state
N.O.
1xxx,xxxx
24V
Over load state
1xxx,xxxx
0V
Normal state
N.C.
0xxx,xxxx
24V
Normal state
0xxx,xxxx
0V
Over load state
Suitable for car top board switch signal, to fulfill overload and full load needs set F5-36=1.
7.7.2 Main control board switch
’
s terminal inputting mode:
There are 24 switch inputting terminals (CN1, CN9) of NICE 3000 integrated controller
’
s
main control board. Each terminal has more than 60 function selections. Details refer to the
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...