NICE3000 User Manual System typical application and adjustment
159
Put 100% rated load into the car. Adjust the switch position of full load to make full load
switch act but over load switch not. The system memorizes it as full load.
Put 110% rated load into the car. Adjust the switch position of over load. to make over
load switch act. The system memorizes it as over load.
When complete upwards work, lift can be ready to run at high speed.
Test at high speed
4)
Car command testing
a)
Let the lift in self-motion state. Key in signal level command by shortcut key F1 in small
keyboard or function code F7-00 in special control panel. Observe whether the lift runs
according to setting command or not.
External call command testing
b)
Let the lift in self-motion state. Key in external call up and down command by function code
F7-01, F7-02 in special control panel, or press every floor external call. Observe whether the lift
runs according to setting command or not.
Door open and close function testing
c)
When the lift stop at the landing, observe whether the door opens normally or not and whether
door
’
s keeping time meets the requirements or not. When lift responds to call and be to run,
observe whether the door close normally or not.
Fast speed running
5)
After testing at high speed, stop lift and add required functions. Then start adjusting at high
speed.
Set FE-32, FE-33 and F8-08 according to users
’
actual needs.
a)
According to user and actual needs, adjust F6 group parameters; Set service floor, lock
b)
main landing F6-04, fire main landing F6-03, parking main landing F6-02, and group
control, time-sharing control, parallel fastigium control.
Function test of fire return to main landing
c)
If there is the fire return to main landing function availability and the fire main landing is setting,
dial the fire button in the fire landing. Then observe whether the lift can return to the fire landing
normally and the door state meets the requirements.
Firemen run function
d)
If there is fireman running function setting, after the lift
’
s fire returns to the main landing,
dial the fire button and the lift immediately gets into the fireman running state. The lift won
’
t
respond to the external call, and the door machine can only open the door when keep pressing
on the open button. Once release the open button, the door close immediately.
Re-leveling function testing
e)
If the re-leveling function is availability, observe whether the lift can re-level or not and the
re-leveling speed meets the requirements or not. If error is over large, please adjust F3-10
appropriately.
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...