input PE, it should be as small as possible. If it is too large, please check immediately.
7.1.2 Adjusting on the slow speed running lift
After the external inspection, get rid off the brake control wire, close the power, and observe no
outputting of the brake control terminal when the lift is not in running state. Even if the brake
control wire is connected, the brake won
’
t open. Then cut off the power, and connect the
brake control wire. Prepare for slow speed running.
Check after power-on
1)
Check the voltage between COM and the input terminal (CN3 24V)on the main control
a)
board, It should be within DC24V
±
15%.
Check power of inside and outside calling, within DC24V
±
15%.
b)
Check the voltage between 15V and PGM of CN6, value: DC15V
±
2%.
c)
Check the parameters setting function of group F5
2)
Terminal function parameter F5, decides whether the received signal is corresponding with
signal sent to system, and whether the expected control aim is the same with the real control
aim.
Please check according to the factory drawing whether the function of every terminal is
a)
correct, and whether the input type and output type are the same with the reality.
We can confirm whether the input state of corresponding terminal is correct by the lamp
b)
state and setting type of corresponding input and output terminals on the main control
board
Motor tuning
3)
Motor tuning must be in operation panel control model. Before tuning, please input parameter
F1-00~F1-05. NICE 3000 elevator integrated controller matches standard motor parameters
according to the nameplate parameter; distance-control mode depends on motor parameter
deeply. To gain good control features, the motor parameter inputted must be correct. Details of
tuning are described in chapter 6 and the application of synchronous motor in this chapter.
Before the tuning of the synchronous motor, make sure the encoder has
completed the installation and wiring. After the tuning of the synchronous motor, make sure the
synchronous motor runs normally and then recover the wire rope.,
Door machine adjust
4)
Check the connection of the door machine according to the instruction and the types of
a)
door machines. Measure the door machine
’
s power. Move the car into the door-area.
Turn off the door machine
’
s power. Place the door machine at adjustment state. Drive
the land-door by door-machine. Observe door machine
’
s running direction, running
speed, torque, whether crash exists or not, and whether the door opens to the right
position. Adjust door machine
’
s parameters to make it run normally.
Set FB-00
、
FB-02~FB-05 according to the fact. Set FB-06
、
FB-08 according to width
b)
and speed of the door. Leave some allowance to avoid frequent protection of door
machine. Set FB-09~FB-14 correctly to make the door running meet people
’
require
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...