Function parameter description NICE3000 User Manual
130
F6-08
Lift number
Default
1
Min. Unit
1
Setting Range
1
~
8
It can set lift number when using group control. When F6-07 = 1, this function is useless.
1
:
Lift 1.At this time, the car top panel default is lift 1 which means the first three are set as
OFF. This lift is the main lift of parallel, and it complete mostly parallel logic count.
2
:
Lift 2.At this time, the 1, 2 bit of car top panel switch S1 should be set as ON.
If it is in group control state, this function code should be set according to the actual coding of
the lift. Details please refer to the instruction of <MCTC-GCB-A>.
F6-09
Parallel selection
Default
0
Min. Unit
0
Setting Range
1~2
Bit0: separated staying function selection
Bit1: Reserved
Bit2: CN2 parallel. There are two ways to parallel, BIT2=1 uses CN2 to parallel.
Note: When it doesn
’
t use CN2 for parallel, please make sure the BIT2=0, otherwise, the
controller may not run normally!
F6-13
Chucker-out floor
Default
1
Min. Unit
1
Setting Range
The lowest landing(F6-01)
~
The highest landing(F6-00)
It can set lift chucker-out floor. The chucker-out floor is availability from 10 at night to 6 at
morning. Every time lift will run to the chucker-out floor firstly, then stop and open the door.
Then it will run to the target floor, it can increase security. Using this function or not, please set
through FE-32.
Function code
Name
Default
Min. Unit
Setting Range
F6-14
down-collective 1 start time
00
:
00
00
:
01
00
:
00
~
23
:
59
F6-15
down-collective 1 end time
00
:
00
00
:
01
00
:
00
~
23
:
59
F6-16
down-collective 2 start time
00
:
00
00
:
01
00
:
00
~
23
:
59
F6-17
down-collective 2 end time
00
:
00
00
:
01
00
:
00
~
23
:
59
These four function parameters define two groups of down-collective time segmentation. In this
two time segmentation, lift will run according to the down-collective mode, which means it only
responds to down external call.
Function code
Name
Default
Min. Unit
Setting Range
F6-18
Time-sharing service 1
start time
00
:
00
00
:
01
00
:
00
~
23
:
59
F6-19
Time-sharing service 1
end time
00
:
00
00
:
01
00
:
00
~
23
:
59
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...