
Function parameter description NICE3000 User Manual
152
C. External call for current floor opening the door: After the lift close the door, the current floor
has the re-opening function.
D. Open the door when stops: When the lift stops, it
’
s judged according to several conditions:
If there
’
s only single side external call, the lift stops and opens the door that is calling; If there
are two sides external call, the lift stops and judges to open the door according to door1 and
door2 control switch; If there
’
s no external call, but internal call, the lift judges to open the
door according to door1 and door2 control switch when the life stops;
E. After selection of this function, the highest floor of the fifteenth floor (physical floor). External
call address 1~15 corresponds to Floor 1~15 door 1 external call, and external call address
17~31 corresponds to Floor 17~31 door 2 external call.
6.16 FE Group Factory Parameters (Reserved)
6.17 FP Group User Parameters
FP-00
User password
Default
0
Min. Unit
1
Setting Range
0
~
65535
Set any number but zero, the password protection function is valid.
00000: Clear the password value setting by previous user, and make the password protection
function invalidation.
After the user password is set and valid, when it gets into the parameter setting state, you
can
’
t check or modify the parameters if the password is not correct. Details of password
setting measures are listed in section 4.2.4.
Please firmly remember your setting password, and contact with the factory if you miss-set or
forget.
FP-01
Parameter resetting
Default
0
Min. Unit
1
Setting Range
0
、
1
、
2
0: None;
1: Return to factory parameters. All the values of other function parameters but F1 group
function code will return to factory parameters. Please operate with caution!
2: Clear memory parameter. It will clear all the recorded error information.
FP-02
User setting examination
Default
0
Min. Unit
1
Setting Range
0
、
1
0: Invalidation
1: Valid, and the operation keyboard only displays those parameters different from factory
setting.
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...