NICE3000 User Manual System typical application and adjustment
169
function codes need setting:
Function code
Name
Setting Range
Setting when parallel
F5-29
Y4 function selection
0~14
14
7.5.3 Parallel lift
’
s case instruction
After the two lifts are in parallel, when the stopping position of the two lifts is different, the lift
’
s
external call dial is different from that of single lift running. When the lift adjustment is completed
and gets into the parallel function adjustment step, generally connect the parallel wiring
according to the former description and set the car top dial code and main control board output
setting. But in some special condition, special disposal is needed. Several typical examples are
listed in the following, and it can flexibly apply according to the examples.
For example: Suppose that there are two lifts in parallel, the No.1 lift stops at Floor B1, Floor
1, Floor 2, and Floor 3; the No. 2 lift stops at Floor 1, Floor 3, and Floor 4; Now the two lifts are
both setting parallel according to section 7.5.1 and 7.5.2. The required special setting is listed
as follows:
Floor dial code setting, display setting
When two lifts are in parallel, if the floor structure is different, the counting of the
floor is according to the lowest floor
’
s minimum value to the highest floor
’
s maximum value,
and corresponding dial code is according to the lowest floor
’
s minimum value, cumulated by
the physical floor. The overlapped service floor zone still needs install leveling plate in the shaft
even if the lift doesn
’
t stop at this floor. Set the service floor to make the lift doesn
’
t stop at
this floor. In the example, Floor 1 and Floor 3 are in the overlapped service floor zone, but No.2
lift
’
s Floor 2 doesn
’
t have the floor door, which means it doesn
’
t serve the Floor 2, but this
floor still needs install leveling plate.
The corresponding setting of No.1 lift:
1
2
3
4
8
Physical floor
Display setting
B1
ON
OFF
OFF
OFF
ON
1
FE-01=1101
1
OFF
ON
OFF
OFF
OFF
2
FE-02=1901
2
ON
ON
OFF
OFF
OFF
3
FE-03=1902
3
OFF
OFF
ON
OFF
OFF
4
FE-04=1903
The corresponding setting of No.2 lift:
1
2
3
4
8
Physical floor
Display setting
1
OFF
ON
OFF
OFF
ON
2
FE-02=1901
2
Not service, but must installation leveling plate
FE-03 =1902
3
OFF
OFF
ON
OFF
OFF
4
FE-04=1903
4
ON
OFF
ON
OFF
OFF
5
FE-05=1904
Bit of
DIP
State
Floor
Bit of
DIP
State
Floor
Summary of Contents for MCTC-CTB-A
Page 12: ...Preface NICE3000 User Manual 12...
Page 15: ...Safety information and attention items 1...
Page 21: ...Product information 2...
Page 29: ...3 Structure of the control system and the component introduction...
Page 69: ...4 Installation and wiring...
Page 80: ...Installation and wiring NICE3000 User Manual 80...
Page 81: ...5 Function parameters tables...
Page 100: ...Function parameters tables NICE3000 User Manual 100...
Page 101: ...6 Function parameter description...
Page 153: ...7 System typical application and adjustment...
Page 172: ...System typical application and adjustment NICE3000 User Manual 172...