Connectors and binectors
01.04
12-8
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Connector Description
Normalization
Function
diag., Sheet
K0988
Firing pulse cycle time (time difference between current and previous firing
instant) in T1 increments of 1.334 µs each
K0989
Information about torque direction and firing angle
Nibble 0 .. Torque direction
0 = M0 (--)
1 = MI
2 = MII
9 = Reserved
Nibble 1 .. Code number for firing angle
1 = Requested firing angle has been implemented
2 = Reserved
3 = Firing angle at 180°
4 = Firing angle at 180°
5 = Requested firing angle cannot be implemented because of
strong pulse compression
6 = Reserved
7 = Reserved
8 = Reserved
Nibble 2 .. Code number for requested torque direction
0: Not
RUN
(
≥
o1.0)
1: Torque direction acc. to current setpoint (==> M0, MI, MII)
2: Reserved
3: Reserved
4: Additional wait time in auto-reversing stage (==> M0)
5: Current has reached 0 (==> M0), phase reversal permitted
6: Current not yet 0 (==> M0), phase reversal not permitted
yet
7: Reserved
8: Reserved
9: Reserved
A: Wait for rotor contactor to switch (==> M0)
B: Reserved
C: Reserved
D: Reserved
E: Reserved
F: Reserved
Nibble 3 .. Code number for zero current signal
[SW 1.9 and later]
0: The "I=0" signal is not evaluated because no change in
torque direction is required
1: I <> 0
2: I = 0 for less than 0.1 msec
3: I = 0 for more than 0.1 msec
4: I = 0 for more than 0.6 msec
5: Ia-act (K116) is < 1 % for more than 6 current peaks
K0990
Current total processor capacity utilization (C167)
K0991
Projected total processor capacity utilization (C167) for maximum line
frequency (65Hz)
K0992
Current total processor capacity (C167) utilized by background routines
K0994
Total processor capacity (C167) currently utilized by routines synchronized
with firing pulses
Serial interface 1 (USS1 on G-SST1)
K2001
USS1 receive data, word 1
1
=
∧
1
G170
K2002
USS1 receive data, word 2
1
=
∧
1
G170
K2003
USS1 receive data, word 3
1
=
∧
1
G170
K2004
USS1 receive data, word 4
1
=
∧
1
G170
K2005
USS1 receive data, word 5
1
=
∧
1
G170
K2006
USS1 receive data, word 6
1
=
∧
1
G170
K2007
USS1 receive data, word 7
1
=
∧
1
G170
K2008
USS1 receive data, word 8
1
=
∧
1
G170
K2009
USS1 receive data, word 9
1
=
∧
1
G170
K2010
USS1 receive data, word 10
1
=
∧
1
G170
K2011
USS1 receive data, word 11
1
=
∧
1
G170
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......