P555
*
FDS
(G151)
Source for the Influencing quantity of the droop adaptation
[SW 1.7 and later]
Selection of which connector is connected at the influencing quantity for
adaptation of the n controllers droop
0 = Connector K0000
1 = Connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P556
FDS
(G151)
Adaptation of n controller P gain: Threshold 1
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P557
FDS
(G151)
Adaptation n controller integration time: Threshold 1
[SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P558
FDS
(G151)
Adaptation n controller droop: Threshold 1
[SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P559
FDS
(G151)
Adaptation of n controller P gain: Threshold 2
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P560
FDS
(G151)
Adaptation n controller integration time: Threshold 2
[SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P561
FDS
(G151)
Adaptation n controller droop: Threshold 2
[SW 1.7 and later]
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Speed controller - speed droop limitation
P562
FDS
(G151)
Positive speed droop limitation
0.00 to 199.99
[%]
0.01%
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
P563
FDS
(G151)
Negative speed droop limitation
-199.99 to 0.00
[%]
0.01%
Ind: 4
FS=-100.00
Type: I2
P052 = 3
P051 = 40
Online
11.31 Input quantities for signals
(see also Section 8, Sheets G187 and G188)
P590
*
(G187)
Source for setpoint of “nset = nact signal 1”
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "nset" for the
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=174
Type: L2
P052 = 3
P051 = 40
Offline
P591
*
(G187)
Source for actual value of "n-set = n-act signal 1"
Setpoint/actual value deviation signal:
Selection of connector to be injected as input quantity "nact" for the
setpoint/actual value deviation signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
P592
*
(G187)
Source for actual value of "n < ncomp. signal”
n < ncomp. signal:
Selection of connector to be injected as input quantity (n) for the
n < ncomp. signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
P593
*
(G188)
Source for actual value of “n < nmin signal”
n < nmin
signal:
Selection of connector to be injected as input quantity (n) for the n < nmin
signal.
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=167
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...