Function descriptions
01.04
9-6
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Data sets
See also Section "Switch over parameter sets"
Switch over function parameters (function data sets):
4 different sets of some parameters (function parameters) are available and can be selected by means
of the "Switch over function parameters" function. The switchover operation is controlled by control
word 2 (bits 16 and 17, see Section 8, Sheet G181 and G175). Index .01, .02, .03 or .04 of these
parameters is operative depending on the status of the control bit.
The parameters of this parameter set are identified by an ".F" next to the parameter number in the
function diagrams and by "FDS" under the parameter number in the tabulated parameter list.
The parameters belonging to the function parameter set must not be confused with other parameters
which, by chance, also have 4 indices. The latter parameters are not affected by the "Switch over
function parameters" function.
Switch over binector and connector parameters (Bico data sets):
2 different sets of some selection switches are available and can be selected by means of the "Switch
over binector and connector parameters" function. The switchover function is controlled by control
word 2 (bit 30, see Section 8, Sheet G181 and G175). The status of the control bit determines whether
index.01 or index .02 of the parameter is operative.
The parameters of the Bico data set are identified by a ".B" next to the parameter number in the
function diagrams and by "BDS" under the parameter number in the tabulated parameter list.
The parameters belonging to the Bico data set must not be confused with other parameters which, by
chance, also have 2 indices. The latter parameters are not affected by the "Switch over binector and
connector parameters" function.
Display parameter
The values of certain signals can be output using display parameters (r parameters, n parameters).
Connector displays (Section 8, Sheet G121) can be used to link all connectors with display parameters
so that they can be displayed.
Representation in function diagrams:
Apart from the parameter number, the function diagrams may also include a function description for
the parameter as supplementary information.
r316
RFG status
Display parameter
Parameter number = r316
Display of RFG (ramp-function generator) status
9.2 Computation
cycles, time delay
Functions associated with analog inputs, analog outputs, binary inputs, binary outputs and interfaces,
as well as function blocks associated with the motorized potentiometer, setpoint generation, ramp-
function generator and closed-loop speed and current controls, are called up and calculated in
synchronism with the firing pulses (i.e. every 3.333 ms at a line frequency of 50 Hz).
The parameter settings are processed in a further computation cycle with a cycle time of 20ms.
With regard to the transfer of parameter values via interfaces, it is important to remember that some
transferred parameters must be converted to this 20 ms cycle before they can be applied, for example,
in the firing pulse cycle.
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......