01.04
Faults / alarms
SIEMENS AG 6SG7000-0BA76
10-17
SIMOTRAS HD Operating Instructions
Alarm
Description
A039 I2t value of power section too high
(active in all operating states)
This alarm is activated if the permissible I2t value
for the relevant power section is reached. At the same time, the current limit is
set to P077 * 100% of the converter rated current. This limit is not cancelled again until the setpoint drops below 100% of the
converter rated current. See also Fault F039 and Parameter P075.
A044
An alarm is active on one slave connected to the paralleling interface
[V2.1
and
later]
(active in all operating states)
A046
Analog select input for main setpoint (terminals 4 and 5) faulty
(active in operating states of
≤
o6)
This alarm is activated when P700=2 (current input 4 to 20 mA) and the input current is less than 3mA.
A047
Analog select input 1 (terminals 6 and 7) faulty
(active in operating states of
≤
o6)
This alarm is activated when P710=2 (current input 4 to 20 mA) and the input current is less than 3mA.
A049
SCB1: No SCI slave connected
(active in all operating states)
A050
SCB1: Not all required SCI slaves are available
(active in all operating states)
The SCI slave required to perform the parameterized functions is not available
A053
Alarm message from free function block FB258
(active in all operating states)
The binector connected via parameter U106 Index.002 is in the log. "1" state
A054
Alarm message from free function block FB259
(active in all operating states)
The binector connected via parameter U107 Index.002 is in the log. "1" state
A067 Converter
cooling
faulty
(active in all operating states)
The heatsink temperature is > 90 °C.
The monitoring function is activated 6s after the electronics supply is connected.
(The current heat sink temperature is indicated at parameter r013 and on connector K050)
A081
to
A088
CB alarm of 1
st
CB
(active in all operating states
≤
o11)
The meaning of these alarms depends on the type of board used.
For further information, refer to Section 7.10, Start-Up of Optional Supplementary Boards, in the relevant board description.
A089
to
A096
CB alarm of 2
nd
CB
(active in all operating states
≤
o11)
The meaning of these alarms depends on the type of board used.
For further information, refer to Section 7.10, Start-Up of Optional Supplementary Boards, in the relevant board description.
A097
to
A128
TB alarms
(active in operating states
≤
o11)
For more information about TECH BOARD alarms, please refer to Operating Instructions or Configuring Guide of the relevant
board.
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......