01.04
Parameter list
SIEMENS AG 6SG7000-0BA76
11-149
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
U786
(2786)
(Z118)
(Z119)
Normalization of analog outputs on EB2
%
100
786
U
x
]
V
[
y
∗
=
x = normalization input (corresponds to filtering output)
y = normalization output (corresponds to output voltage at analog output
with an offset of 0)
i001: AO of the first EB2
i002: AO of the second EB2
-200.00 to 199.99
[V]
0.01V
Ind: 2
FS=10.00
Type: I2
P052 = 3
P051 = 40
Online
U787
(2787)
(Z118)
(Z119)
Offset for analog output on EB2
i001: AO of the first EB2
i002: AO of the second EB2
-10.00 to 10.00
[V]
0.01V
Ind: 2
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
n788
(2788)
(Z118)
(Z119)
Display of analog outputs on EB2
i001: AO of the first EB2
i002: AO of the second EB2
-200.0 to 199.99
[%]
0.01%
Ind: 2
Type: I2
P052 = 3
11.82 Configuring the SBP pulse encoder board
U790
(2790)
*
(Z120)
Configuration of input level of A/B and CRTL tracks
0: HTL
unipolar
1: TTL
unipolar
2: HTL
differential
input
3:
TTL/RS422 differential input
0 to 3
1
Ind: None
FS=1
Type: O2
P052 = 3
P051 = 40
Offline
U791
(2791)
*
(Z120)
Configuration of encoder supply voltage
The supply is subject to a current limit of 250mA
Caution:
Setting the parameter incorrectly can damage the encoder
(i.e. 15 V voltage for an encoder which requires a 5 V supply).
0:
5V voltage supply
1: 15V
voltage
supply
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U792
(2792)
*
(Z120)
Number of pulses per revolution
Number of lines on one track around circumference of disk
100 to 20000
1
Ind: None
FS=1024
Type: O2
P052 = 3
P051 = 40
Offline
U793
(2793)
*
(Z120)
Encoder type
0:
Encoder with A/B track (two tracks displaced by 90 degrees)
1:
Encoder with separate forward and reverse tracks
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U794
(2794)
(Z120)
Reference speed
When actual speed = reference speed a value of 100% is output in the
appropriate diagnostic parameter (n795) and connector
50.0 to 6500.0
[rev/min]
Ind: None
FS=500.0
Type: O2
P052 = 3
P051 = 40
Online
n795
(2795)
(Z120)
Display of actual speed in % of reference speed
-200.00 to 199.99
[%]
Ind: None
Type: I2
P052 = 3
U796
(2796)
*
S00
(Z120)
Resetting the position counter
[SW 2.0 and later]
Setting the type of resetting for position acquisition
0 = free-running (no reset)
1 = see function diagram Z120
2 = see function diagram Z120
0 to 2
1
Ind: none
FS=0
Type: O2
P052 = 2
P051 = 40
Online
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......