01.04
Parameter list
SIEMENS AG 6SG7000-0BA76
11-105
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
Setpoint branching
(output = K9235)
The input quantity is weighted with 2 parameters:
Parameter U297 determines the output value with an input = 0%
Parameter U298 determines the output value with an input = +100%
-U297 and -U298 apply in the case of negative input values.
The hysteresis set in parameter U299 is applied for transitions from negative to positive input values and vice versa
U296
(2296)
*
S00
(B161)
Source for input quantity
FB 112
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U297
(2297)
S00
(B161)
Minimum speed
FB 112
0.00 to 199.99
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U298
(2298)
S00
(B161)
Maximum speed
FB 112
0.00 to 199.99
[%]
0.01
Ind: None
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
U299
(2299)
S00
(B161)
Hysteresis FB
112
0.00 to 100.00
[%]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
11.61 Simple ramp-function generator
Please note: The output (y) = 0 is set in response to "Set simple ramp-function generator to zero" and POWER ON
The output (y) is frozen at the current value in response to "Stop simple ramp-function generator"
The ramp-up and ramp-down times are set to zero in response to "Bypass simple ramp-function generator"
Ramp-up integrator:
The simple ramp-function generator contains a flip-flop whose output is set to log. "0" (ramp generator initial run) after
POWER ON or when the ramp-function generator has been enabled. When the ramp-function generator output reaches a
value corresponding to the input quantity (y=x) for the first time, the flip-flop output switches to log. "1" and remains in this
state until the next enabling command. This output is linked to binector B9191. By parameterizing U301, index i001=919, it
is possible to apply this binector to the "Bypass simple ramp-function generator" function and thus to implement a ramp-up
integrator function.
U300
(2300)
*
S00
(B165)
Source for input quantity
FB 113
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U301
(2301)
*
S00
(B165)
Source for control signals
FB 113
i001
Source for "Bypass simple ramp-function generator" signal
i002
Source for "Stop simple ramp-function generator" signal
i003
Source for "Reset / enable simple ramp-function generator"
signal (0 = reset to zero, 1 = enable)
Settings:
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 3
FS=
i001: 0
i002: 0
i003: 1
Type: L2
P052 = 3
P051 = 40
Offline
U302
(2302)
S00
(B165)
Ramp-up time
FB 113
0.00 to 300.00
[s]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
U303
(2303)
S00
(B165)
Ramp-down time
FB 113
0.00 to 300.00
[s]
0.01
Ind: None
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......