Faults / alarms
01.04
10-4
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
Fault value:
r047 Index 002 to 016:
1
Undervoltage has occurred
i002 Number of phase that has activated fault message
0 ... Phase
UV
1 ... Phase
VW
2 ... Phase
WU
i003 Incorrect voltage value (normalized to 16384)
4
Undervoltage persists for longer than time set in
parameter P086 (if this is set to >0)
-
F007 Overvoltage
(active in operating states of
≤
o4)
The voltage at terminals U1, V1 or W1 is higher than the response threshold (for longer than the “restart time” set in P086).
Response threshold for supply voltage:
)
100%
P352
(1
P078.001
+
∗
Possible causes of fault
•
Line
overvoltage
•
Monitoring values set too sensitively or incorrectly (P352, P078)
Fault value:
r047 Index 002 to 016:
1 Overvoltage
has
occurred
i002 Number of phase that has activated fault message
0 ... Phase
UV
1 ... Phase
VW
2 ... Phase
WU
i003 Incorrect voltage value (normalized to 16384)
4
Overvoltage persists for longer than time set in
parameter P086 (if this is >0)
-
F008
Line frequency less than the minimum line frequency acc. to parameter P363
(active in operating states of
≤
o5)
This fault message is activated if the line frequency is less than the minimum line frequency
(for longer than the “restart time” set
in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (minimum line frequency) is 45Hz.
Fault
value:
1
Line frequency < minimum line frequency
4
Line frequency less than the minimum line frequency
for longer than set in parameter P086 (if this is >0)
F009
Line frequency greater than the maximum line frequency acc. to parameter P364
(active in operating states of
≤
o5)
This fault message is activated if the line frequency is greater than the maximum line frequency (for longer than the “restart time”
set in parameter P086).
Note: Up to software version 1.7 the threshold for activation of the fault message (maximum line frequency) is 65Hz
Fault
value:
1
Line frequency > maximum line frequency
4
Line frequency greater than the maximum line frequency for longer than set in parameter P086 (if >0)
10.1.2.2 Interface error
F011
Telegram failure at GSST1
when P780 = 2:
USS telegram failure at G-SST1
(active from the first receipt of a valid protocol in all operating states)
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P787.
Possible causes of fault
•
Cable break
•
Error in USS master
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......