Appendix
01.04
18-2
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Term. 81/82 (MB .. ready message)
U621.001 = 162
[G119.3]
U621.002 = 162
[G119.3]
Term. 83/84 (ST .. setpoint in controlled
range)
U622.001 = 540
[G119.3]
U622.002 = 540
[G119.3]
Term. 85/86 (BR .. n
≥
n_min)
U623.001 = 165
[G119.3]
U623.002 = 165
[G119.3]
Term. 87/88 (S1 .. rotor contactor stage 1)
[G119.4]
Term. 89/92 (S2 .. rotor contactor stage 2)
For SIMOTRAS HD this is Term. 89/90
[G119.4]
Term. 90/92 (S3 .. rotor contactor stage 3)
For SIMOTRAS HD this is Term. 91/92
[G119.4]
Term. 91/92 (S4 .. rotor contactor stage 4)
For SIMOTRAS HD this is Term. 93/94
[G119.4]
Terminals 90, 92 and 94 must be linked
Term. 11/22 (MW .. message “temperature
pre-warning”)
For SIMOTRAS HD this is Term. 109/110 [G112.6]
U619.001 = 148
[G112.3]
U619.002 = 148
[G112.3]
Potentiometer on SIMOTRAS HE
(6GA4625 series)
Corresponding parameter on SIMOTRAS HD
(6SG70 series)
TF – Delayed enable
P319 (factory setting = 0.05 s)
[G136.2]
TZ – Brake application time monitoring
This function must be implemented using free
modules if required (similar to ramp-down
monitoring on Sheet K15 in Section 8)
NT – Tachometer voltage normalization
P741 (factory setting = 60.00 V)
[G113.2]
NS – Speed setpoint normalization
P320 (factory setting = 100.00 %)
[G135.2]
SH – Lift start pulse
U651 (factory setting = 0.00 %)
[G150.2]
NZ – Additional setpoint normalization
No setting necessary as the “zero delay angle”
function is implemented in a different way.
HR – Clockwise acceleration ramp
P303 (factory setting = 10.00 s) *)
[G136.2]
AR – Clockwise deceleration ramp
P304 (factory setting = 10.00 s) *)
[G136.3]
HL – Anticlockwise acceleration ramp
P303 (factory setting = 10.00 s) *)
[G136.2]
AL – Anticlockwise deceleration ramp
P304 (factory setting = 10.00 s) *)
[G136.3]
VR – n controller gain
P225 (factory setting = 3.00)
[G151.2]
ND – Speed monitoring normalization
P388 (factory setting = 5.00 %)
[G187.5]
ST – Setpoint in controlled range
U628 (factory setting = 55.0 %)
[G160.6]
BR – Standstill monitoring
P370 (factory setting = 5.00 %)
[G188.4]
S1 – Switching logic rotor contactor stage 1 U630 (factory setting = - 1.0 %)
[G119.2]
S2 – Switching logic rotor contactor stage 2 U634 (factory setting = 50.0 %)
[G119.6]
S3 – Switching logic rotor contactor stage 3 U636 (factory setting = 75.0 %)
[G119.6]
S4 – Switching logic rotor contactor stage 4 U638 (factory setting = 90.0 %)
[G119.6]
*) If the ramp-up and ramp-down functions for clockwise and anti-clockwise rotation are to be set
separately, the function data set must be switched over.
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......