Parameter list
SIEMENS AG 6SG7000-0BA76
11-131
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
U640
(2640)
Wait period when switching rotor contactors
i 001: Pick-up time of rotor contactors
i 002: Drop-out time of rotor contactors
i 003: Pick-up time of rotor contactors
(see header for parameter U641 ff.)
Off-load switching is recommended to increase the service life of the rotor
contactors.
A disadvantage of off-load switching of rotor contactors: there is a torque-
free interval, and this may lead to a deviation in the speed.
Whenever a rotor contactor is switched in, the firing pulses are disabled for
the time set at index 001 (zero current interval).
Whenever a rotor contactor is switched out, the firing pulses are disabled
for the time set at index 002 (zero current interval).
0 to 2000
[ms]
1ms
Ind: 3
FS=
i001: 0
i002: 0
i003: 50
Type: O2
P052 = 3
P051 = 40
Online
Preventing current peaks during rotor stage stepping:
To prevent excessive stator current values occurring when switching in the next rotor contactor, it is desirable, at the same time as the
contactor is switched in (delayed by the time set at U640 index 003), to reduce the I component of the speed controller by roughly the
same proportion by which the rotor resistance is also reduced.
U641
(2641)
FDS
Factor for I component n controller with rotor stage 1
R (stage 1) / R (counter-torque stage)
0.0 to 100.0
[%]
0.1%
Ind: 4
FS=50.0
Type: O2
P052 = 3
P051 = 40
Online
U642
(2642)
FDS
Factor for I component n controller with rotor stage 2
R (stage 2) / R (stage 1)
0.0 to 100.0
[%]
0.1%
Ind: 4
FS=50.0
Type: O2
P052 = 3
P051 = 40
Online
U643
(2643)
FDS
Factor for I component n controller with rotor stage 3
R (stage 3) / R (stage 2)
0.0 to 100.0
[%]
0.1%
Ind: 4
FS=50.0
Type: O2
P052 = 3
P051 = 40
Online
U644
(2644)
FDS
Factor for I component n controller with rotor stage 4
R (stage 4) / R (stage 4)
0.0 to 100.0
[%]
0.1%
Ind: 4
FS=50.0
Type: O2
P052 = 3
P051 = 40
Online
U645
(2645)
FDS
(G151)
Factor for P component n controller with counter-torque operation
effective P gain for speed controller with counter-torque operation = P225 *
U645
1 to 1000
[%]
1%
Ind: 4
FS=100
Type: O2
P052 = 3
P051 = 40
Online
U646
(2646)
FDS
(G151)
Factor for P component n controller with rotor stage 1
effective P gain for speed controller with rotor stage 1 = P225 * U646
1 to 1000
[%]
1%
Ind: 4
FS=100
Type: O2
P052 = 3
P051 = 40
Online
U647
(2647)
FDS
(G151)
Factor for P component n controller with rotor stage 2
effective P gain for speed controller with rotor stage 2 = P225 * U647
1 to 1000
[%]
1%
Ind: 4
FS=100
Type: O2
P052 = 3
P051 = 40
Online
U648
(2648)
FDS
(G151)
Factor for P component n controller with rotor stage 3
effective P gain for speed controller with rotor stage 3 = P225 * U648
1 to 1000
[%]
1%
Ind: 4
FS=100
Type: O2
P052 = 3
P051 = 40
Online
U649
(2649)
FDS
(G151)
Factor for P component n controller with rotor stage 4
effective P gain for speed controller with rotor stage 4 = P225 * U649
1 to 1000
[%]
1%
Ind: 4
FS=100
Type: O2
P052 = 3
P051 = 40
Online
11.73 Start pulse, speed controller
(see also Section 8, Sheet G150)
U651
(2651)
FDS
(G150)
Start pulse
(integrator setting value for the speed controller)
-100.00 to 100.00
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
U652
(2652)
FDS
(G150)
Multiplier for start pulse when lowering
when start pulse as in U651 is also used for a positive setpoint (lowering)
0.00 to 100.00
[%]
0.01%
Ind: 4
FS=50.00
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......