Faults / alarms
01.04
10-8
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.6 External faults
Fault message from free function block FB4
(active in all operating states)
Fault value:
F033
1
the binector wired via parameter U102 Index.001 is in the state log.”1”
2
the binector wired via parameter U102 Index.002 is in the state log.”1”
3
the binector wired via parameter U102 Index.003 is in the state log.”1”
4
the binector wired via parameter U102 Index.004 is in the state log.”1”
Fault message from free function block FB5
(active in all operating states)
Fault value:
F034
1
the binector wired via parameter U103 Index.001 is in the state log.”1”
2
the binector wired via parameter U103 Index.002 is in the state log.”1”
3
the binector wired via parameter U103 Index.003 is in the state log.”1”
4
the binector wired via parameter U103 Index.004 is in the state log.”1”
10.1.2.7 Drive faults
F035 Drive
blocked
(active in operating states of – –, I, II)
The monitoring function responds if the following conditions are fulfilled for longer than the time set in parameter P355:
•
Positive or negative current limit reached
•
Stator current is greater than 1% of converter rated DC current
•
The actual speed value is less than 0.4% of maximum speed
Possible causes of fault
•
Drive blocked
F036
No stator current can flow
(active in operating states of – –, I, II)
This monitoring function responds if the firing angle is at 0° for more than 500 ms and the stator current is less than 1% of the
converter rated DC current.
Possible causes of fault
•
Break in motor cable
F037 I2t motor monitor has responded
(active in operating states of – –, I, II)
This monitoring function responds when an I2t value is reached which corresponds to the final temperature at 110% of the rated
motor current.
Possible causes of fault
•
Parameter P114 is incorrectly set
•
Drive has been operating for too long at >110% of rated motor current
F038 Overspeed
(active in operating states of – –, I, II)
This fault message is activated if the actual speed value (selected in P595) exceeds the positive (P380) or negative (P381)
threshold by 0.5%.
Possible causes of fault
•
Lower current limit has been input
•
Current-controlled operation
•
P512, P513 are set too low
•
Tachometer cable contact fault in operation close to maximum speed
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......