Parameter list
01.04
11-70
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
r814
(G172)
(G174)
Receive data on G-SST3
When USS protocol (P800=2) is selected:
Display of data received via
USS interface 3
i001: Display process data word 1
...
i016
Display process data word 16
i017: Display parameter data word 1
...
i020: Display parameter data word 4
When peer-to-peer (P800=5) is selected:
Display of data received via
peer-to-peer interface 3
i001: Receive data word 1
...
i005
Receive data word 5
i006: Not
in
use
...
i020 Not
in
use
0000 to FFFF H
1
Ind: 20
Type: L2
P052 = 3
r815
(G172)
(G174)
Transmit data on G-SST3
When USS protocol (P800=2) is selected:
Display of the data to be transmitted via
USS interface 3
i001: Display process data word 1
...
i016
Display process data word 16
i017: Display parameter data word 1
...
i020: Display parameter data word 4
When peer-to-peer (P800=5) is selected:
Display of the data to be transmitted via
peer-to-peer interface 3
i001: Transmit data word 1
...
i005
Transmit data word 5
i006: Not
in
use
...
i020 Not
in
use
0000 to FFFF H
1
Ind: 20
Type: L2
P052 = 3
Peer-to-peer interfaces: Enable transmission and receipt of telegrams:
If transmission on a peer-to-peer interface is disabled, the associated output drivers are connected to high impedance.
If reception is disabled on a peer-to-peer interface, then the telegram failure monitoring function is deactivated.
P816
*
(G173)
Peer-to-peer 2: Source for data reception enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P817
*
(G173)
Peer-to-peer 2: Source for data transmission enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P818
*
(G174)
Peer-to-peer 3: Source for data reception enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
P819
*
(G174)
Peer-to-peer 3: Source for data transmission enabling command
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......