Connectors and binectors
01.04
12-24
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
12.2 Binector
list
The states of binectors can be displayed via parameters r045 and P046.
Binector
Name, description
Function
diag., Sheet
Fixed values
B0000
Fixed value 0
G120
B0001
Fixed value 1
G120
Binary inputs, terminals 36 to 43
B0010
Status of terminal 36
G110
B0011
Status of terminal 36, inverted
G110
B0012
Status of terminal 37
G110
B0013
Status of terminal 37, inverted
G110
B0014
Status of terminal 38
G110
B0015
Status of terminal 38, inverted
G110
B0016
Status of terminal 39
G110
B0017
Status of terminal 39, inverted
G110
B0018
Status of terminal 40
G110
B0019
Status of terminal 40, inverted
G110
B0020
Status of terminal 41
G110
B0021
Status of terminal 41, inverted
G110
B0022
Status of terminal 42
G110
B0023
Status of terminal 42, inverted
G110
B0024
Status of terminal 43
G110
B0025
Status of terminal 43, inverted
G110
Binary inputs, terminals 211 to 214
B0040
Status of terminal 211
G186
B0041
Status of terminal 211, inverted
G186
B0042
Status of terminal 212
G186
B0043
Status of terminal 212, inverted
G186
B0044
Status of terminal 213
G186
B0045
Status of terminal 213, inverted
G186
B0046
Status of terminal 214
G186
B0047
Status of terminal 214, inverted
G186
Analog inputs
B0050
Analog input, terminal 4: 1 = Open circuit (i
≤
2 mA)
G113
B0051
Analog input, terminal 6: 1 = Open circuit (i
≤
2 mA)
G113
Pulse encoder evaluation
B0052
Fault in digital speed sensing circuit
G145
B0053
Underflow of actual position value
[SW 1.9 and later]
This binector changes to 1 when connector KK0046 (actual position value extended in software to a 32-bit
value) counts from value 8000 0000H (= –2
31
) to value 7FFF FFFFH (= +2
31
–1).
Binector B0053 does not change back to 0 until connector KK0046 assumes a value other than 7FFF
FFFFH (= +2
31
–1) again.
G145
B0054
Overrflow of actual position value
[SW 1.9 and later]
This binector changes to 1 when connector KK0046 (actual position value extended in software to a 32-bit
value) counts from value 7FFF FFFFH (= +2
31
–1) to value 8000 0000H (= –2
31
).
Binector B0054 does not change back to 0 until connector KK0046 assumes a value other than 8000
0000H (= –2
31
) again.
G145
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......