PNU
Description
Value range
[Unit]
No. indices See
Change
P182
FDS
(G160)
Positive torque limit 2
If "Torque limit switchover" is selected (state of binector selected in P694
=1) and the speed is higher than the threshold speed set in parameter
P184, then torque limit 2 is activated in place of torque limit 1.
-300.00 to 300.00
[%]
0.01% of rated motor
torque
Ind: 4
FS=300.00
Type: I2
P052 = 3
P051 = 40
Online
P183
FDS
Negative torque limit 2
If "Torque limit switchover" is selected (state of binector selected in P694
=1) and the speed is higher than the threshold speed set in parameter
P184, then torque limit 2 is activated in place of torque limit 1.
-300.00 to 300.00
[%]
0.01% of rated motor
torque
Ind: 4
FS=-300.00
Type: I2
P052 = 3
P051 = 40
Online
P184
FDS
(G160)
Threshold speed for torque limits
If "Torque limit switchover" is selected (state of binector selected in P694
=1) and the speed (K0166) is higher than the threshold speed set in
parameter P184, then torque limit 2 (P182, P183) is activated in place of
torque limit 1 (P180, P181).
0.00 to 120.00
[%]
0.01% of maximum
speed
Ind: 4
FS=0.00
Type: O2
P052 = 3
P051 = 40
Online
P191
FDS
(G162)
Filter time for setpoint for current controller
[SW 1.9
and later]
Filtering of the current setpoint at the input of the current controller.
The purpose of this filter is to decouple the current precontrol from the
current controller.
0 to 10000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
11.11 Speed controller
further parameters for the speed controller P550 - P563
Setting values for speed controller - actual value/setpoint processing
P200
FDS
(G152)
Filter time for actual speed controller value
Filtering of the actual speed value by means of a PT1 element.
0 to 10000
[ms]
1ms
Ind: 4
FS=10
Type: O2
P052 = 3
P051 = 40
Online
P201
FDS
(G152)
Band-stop 1: Resonant frequency
1 to 140
[Hz]
1Hz
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Online
P202
FDS
(G152)
Band-stop 1: Quality
0 Quality
=
0.5
1 Quality
=
1
2 Quality
=
2
3 Quality
=
3
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P203
FDS
(G152)
Band-stop 2: Resonant frequency
1 to 140
[Hz]
1Hz
Ind: 4
FS=1
Type: O2
P052 = 3
P051 = 40
Online
P204
FDS
(G152)
Band-stop 2: Quality
0 Quality
=
0.5
1 Quality
=
1
2 Quality
=
2
3 Quality
=
3
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P205
FDS
(G152)
D element: Derivative-action time
0 to 1000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P206
FDS
(G152)
D element: Filter time
0 to 100
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
r217
(G152)
Indication of the active droop of the speed controller
[SW 1.7 and later]
0.0 to 10.0
[%]
0.1%
Ind: None
Type: O2
P052 = 3
r218
(G151)
(G152)
Indication of the active integration time of the speed controller
[SW 1.7 and later]
0.010 to 10.000
[s]
0.001s
Ind: None
Type: O2
P052 = 3
r219
(G151)
(G152)
Display of effective P gain of speed controller
0.10 to 200.00
0.01
Ind: None
Type: O2
P052 = 3
P221
FDS
(G152)
Speed controller: Hysteresis for speed-dependent PI/P controller
switchover
[SW 1.9
and later]
See P222 for further details.
0.00 to 100.00
[%]
0.01% of maximum
speed
Ind: 4
FS=2.00
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......