01.04
Parameter list
SIEMENS AG 6SG7000-0BA76
11-45
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
P602
*
(G162)
Source for actual current controller value
Selection of connector to be injected as
current controller actual value
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=117
Type: L2
P052 = 3
P051 = 40
Offline
P603
*
(G161)
Source for variable current limit in torque direction I
i001..i004 Selection of connector to be injected as variable current limit
in torque direction I
Normalization: +100% corresponds to P100*P171
i005
Selection of connector to be injected as current limit in torque
direction I with Fast Stop or Shutdown
Normalization: +100% corresponds to P100*P171
i006
Selection of connector to be injected as variable current limit
in torque direction I
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
i007
Selection of connector to be injected as current limit in torque
direction I with Emergency Stop or Shutdown
Normalization: +100% corresponds to r072.002
[can be set in SW 1.9 and later]
Settings:
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 7
FS=
i001: 1
i002: 1
i003: 1
i004: 1
i005: 1
i006: 2
i007: 2
Type: L2
P052 = 3
P051 = 40
Offline
P604
*
(G161)
Source for variable current limit in torque direction II
i001..i004 Selection of connector to be injected as variable current limit
in torque direction II
Normalization: -100% corresponds to P100*P172
i005
Selection of connector to be injected as current limit in torque
direction II with Fast Stop or Shutdown
Normalization: -100% corresponds to P100*P172
i006
Selection of connector to be injected as variable current limit
in torque direction II
Normalization: -100% corresponds to r072.002
[can be set in SW 1.9 and later]
i007
Selection of connector to be injected as current limit in torque
direction II with Emergency Stop or Shutdown
Normalization: -100% corresponds to r072.002
[can be set in SW 1.9 and later]
Settings:
0 = connector K0000
...
8 = connector K0008
9 = value as set in parameter P603.ixx
∗
(
−
1)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 7
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for SIMOTRAS 6SG7050
Page 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Page 603: ......