Ambient Conditions
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
Unrestricted
79
DC8-037-2.02, Edition 10.2017
4.4
Electromagnetic Compatibility
4.4.1 System
Properties
Parameter
Value
Test standard
Product standard
Class
Discharge of static elec-
tricity (ESD)
8 kV-A
6 kV-C
IEC 61000-4-2
IEC 60870-2-1
IEC 60255-26
3
Electromagnetic fields
10 V/m
80 MHz…1 GHz
3 V/m
1…6 GHz
IEC 61000-4-3
IEC 60870-2-1
IEC 60255-26
3
50 Hz magnetic fields
100 A/m (cont.)
1000 A/m (3 s)
IEC 61000-4-8
IEC 60870-2-1
4
Pulse-shaped magnetic
fields
1000 A/m
IEC 61000-4-9
Radio interference voltage
approx. peak value
79 dBµV
(0.15…0.5 MHz)
73 dBµV
(0.5…30 MHz)
CISPR22
IEC 60870-2-1
CISPR22
A
A
Radio interference voltage
mean value
66 dBµV
(0.15…0.5 MHz)
60 dBµV
(0.5…30 MHz)
CISPR22
IEC 60870-2-1
CISPR22
A
A
Radio interference field
strength (10 m) approx.
peak value
40 dBµV/m
(30…230 MHz)
47 dBµV/m
(0.23…2 GHz)
CISPR22
IEC 60870-2-1
CISPR22
A
A
The characteristics required according to the standards IEC 61000-6-2 and IEC 61000-6-4 are
covered by the listed values.
Warning
This is a class A product. In a domestic environment this product may cause radio interference in which
case the user may be required to take adequate measures.