System Components and Technical Data
158
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.3.4 AI-6310
5.7.3.4.1 Functions
•
Temperatures
t1
─
Acquisition of resistance thermometers via analog inputs of a SM-0571
─
Connection of the resistance thermometers: 2-, 3-, or 4-wire technique
─
Update every 400 ms
─
Settable measuring range
−
Temperaturwerte
−
Input range
Pt100: -50…+350°C / -58…+662°F / (
≈
80,31…229,67
Ω
)
Pt100: -100…+700°C / -148…+1292°F / (
≈
60,25…345,13
Ω
)
Ni100: -60…+250°C / -76…+482°F / (
≈
69,5…289,2
Ω
)
−
Resolution
Pt100: -50…+350°C 0.15°C / 0.28°F / (56 m
Ω
)
Pt100: -100…+700°C 0.15°C / 0.28°F / (56 m
Ω
)
Ni100: -60…+250°C 0.15°C / 0.28°F / (56 m
Ω
)
−
Update grid
16
⅔
Hz <6,8 s
50 Hz < 5,6 s
60 Hz < 5,2 s
−
Resistance values
−
Input range 40…400
Ω
−
Resolution 56 m
Ω
−
Update grid
HW rev. ="--"
HW rev.
≥
"-A"
16
⅔
Hz < 6,8 s 16
⅔
Hz < 1,68 s
50 Hz < 5,6 s 50 Hz < 1,44 s
60 Hz < 5,2 s 60 Hz < 1,36 s
─
Revision
─
Noise rejection
─
Automatic calibration
─
Calibration for 2-wire technique
─
Smoothing
─
Adaptation
−
Temperature value (°C, °F), conversion using implemented curves
−
Resistance (
Ω
)
─
Change monitoring
─
Spontaneous transmission of changes